Overview
Update Rate
 controls the rate at which process data is polled and process variables are
calculated. Update Rate = Special produces faster and “noisier” response to changes in the
process. Do not use Special mode unless required by your application.
Prerequisites
Before setting Update Rate to Special:
Check the effects of Special mode on specific process variables.
Contact Micro Motion.
Procedure
Set Update Rate as desired.
Option Description
Normal
All process data is polled at the rate of 20 times per second (20 Hz).
All process variables are calculated at 20 Hz.
This option is appropriate for most applications.
Special
A single, user-specified process variable is polled at the rate of 100 times per second
(100 Hz). Other process data is polled at 6.25 Hz). Some process, diagnostic, and calibra-
tion data is not polled.
All available process variables are calculated at 100 Hz.
Use this option only if required by your application.
If you change Update Rate, the settings for Flow Damping, Density Damping, and Temperature
Damping
 are automatically adjusted.
Effects of Update Rate = Special
Incompatible features and functions
Special
 mode is not compatible with the following features and functions:
Enhanced events. Use basic events instead.
All calibration procedures.
Zero verification.
Restoring the factory zero or the prior zero.
If required, you can switch to Normal mode, perform the desired procedures, and then
return to Special mode.
Process variable updates
Some process variables are not updated when Special mode is enabled.