I/O Wiring – Model 2400S Analog Transmitters
3.4
Wiring the outputs (Zone 1 Exe and Zone 2)
Note: For wiring instructions for Zone 1 Exi transmitters, see Section 3.5.
To wire the outputs:
1. Remove the transmitter housing cover and user interface module. See Section 2.4 for 
instructions.
2. Wire the outputs according to the appropriate wiring diagram:
For mA output wiring diagrams, see Section 3.4.1.
For frequency output wiring diagrams, see Section 3.4.2.
For discrete output wiring diagrams, see Section 3.4.3.
For a discrete input wiring diagram, see Section 3.4.4.
3. Replace the user interface module and transmitter housing cover.
Table 3-1
Terminal configuration options
Channel
Terminals
Function
Power
(1)
(1) For transmitters with Zone 1 Exi approval, I/O power is external only.
Comm
A
1 & 2
mA
Internal
(2)
 or external
(2) Factory default.
HART/Bell 202
B
3 & 4
Frequency
Internal
 or external
None
mA
Internal or external
None
Discrete output
Internal or external
None
Discrete input
Internal or external
None
WARNING
Hazardous voltage can cause severe injury or death.
To avoid the risk of hazardous voltage, shut off the power before wiring the 
transmitter outputs.
WARNING
A transmitter that has been improperly wired or installed in a hazardous area 
could cause an explosion.
To avoid the risk of an explosion:
Make sure the transmitter is wired to meet or exceed local code requirements.
Install the transmitter in an environment that complies with the classification tag 
on the transmitter. See Appendix A.