Emerson 1700 Manuel D’Utilisation

Page de 80
50
Micro Motion
®
 Model 1700 and 2700 Transmitters
Output Wiring – Model 2700 Configurable I/O Transmitters
Figure 6-15
Recommended pull-up resistor versus supply voltage – External power
6.6
Discrete input wiring
Discrete input wiring depends on whether you have configured terminals 5 and 6 (Channel C) for 
internal or external power. The following diagrams are examples of proper wiring for these 
configurations.
If external power is configured, power may be supplied by a PLC or other device, or by direct DC 
input. See Table 6-2 for input voltage ranges.
Table 6-2
Input voltage ranges for external power
VDC
Range
3–30
High level
0–0.8
Low level
0.8–3
Undefined
4400
5
10
15
20
25
30
Supply voltage (Volts)
Ex
tern
al
 p
u
ll
-up
 r
esi
stor
 r
a
ng
e
 (O
hms
)
Recommended 
resistor value range
400
600
800
4200
4000
3800
3600
3400
3200
3000
2800
2600
2400
2200
2000
1800
1600
1400
1200
1000
Note: When using a discrete output to drive a relay, choose 
external pull-up to limit current to less than 500 mA.