Emerson 1700 Manuel D’Utilisation

Page de 80
Installation Manual
55
O
u
tp
ut 
Wi
ri
ng
 – Con
fig
urab
le I
/O
Spec
ifications
Ou
tpu
t W
irin
g
 – Fiel
db
us/PR
O
F
IB
U
S
Output Wiring – Intrinsica
ll
y Saf
e
Appendix A
Specifications
A.1
Functional specifications
The Model 1700 or 2700 transmitter’s functional specifications include:
Environmental requirements
Ambient temperature effect
EMC compliance
A.1.1
Electrical connections
Output connections
The transmitter has two (Model 1700) or three (Model 2700) pairs of wiring terminals for 
transmitter outputs.
The Model 1700/2700 with analog outputs option board has one pair of wiring terminals for 
digital communications (Modbus or HART protocol on RS-485)
On the Model 2700 with F
OUNDATION
 fieldbus or PROFIBUS-PA, terminals 3–6 are not used.
Screw terminals accept one or two solid conductors, 14 to 12 AWG (2,5 to 4,0 mm
2
), or one or two 
stranded conductors, 22 to 14 AWG (0,34 to 2,5 mm
2
).
Power connection
The transmitter has two pairs of wiring terminals for the power connection:
One pair of wiring terminals accepts AC or DC power
One internal ground lug for power-supply ground wiring
Screw terminals accept one or two solid conductors, 14 to 12 AWG (2,5 to 4,0 mm
2
), or one or two 
stranded conductors, 22 to 14 AWG (0,34 to 2,5 mm
2
).
Service port connection
The transmitter has two clips for temporary connection to the service port.