A.5
Environmental effects
Transmitters meet the requirements of the EMC directive 89/336/EEC per EN 61326 Industrial 
(April 1997) when operated at nominal rated flow measurement range. For specific EMC effects 
within the EC, the Technical EMC file may be reviewed at Micro Motion Veenendaal.
To meet the above specifications, the transmitter must be installed with an approved Micro Motion 
sensor, and the sensor cable must be doubly shielded with full-contact glands, or installed in 
continuous, fully bonded metallic conduit. The transmitter and sensor must be directly connected to a 
low-impedance (less than 1 ohm) earth ground. Transmitter outputs must be standard twisted-pair, 
shielded instrument wire.
A.6
Ambient temperature effect on milliamp output
±0.005% of flow rate per °C deviation from output trim temperature
A.7
Shipping weight
Transmitter only: 12.5 lb (5,7 kg)
For flowmeter weights, see sensor specifications
A.8
Hazardous area classifications
For approvals that apply to an individual transmitter, see the hazardous area approvals tag attached to 
the transmitter.
ATEX
When ordered for installation in a Zone 1 (hazardous) area, EEx de[ib] IIB/IIC T6
Otherwise, [EEx ib] IIB/IIC
UL and CSA
Class I, Division 2, Groups A,B,C, and D
Class II, Division 2, Groups F and G