Location of Controls
START-UP 
PROCEDURES
before Start-Up
Safe lighting and other performance criteria were met
with the gas manifold and control assembly provided
on the heater when the heater underwent tests speci-
fied in the latest edition of the ANSI Z21.10.3/CSA 4.3
Standard.
General
Before lighting up a new installation, water should be
flowing  through  the  heater.  Water  pressure  regulator
should be set to minimum 25 PSI.
Initial Start-Up - Pump and
Motor
Many pumps are now direct-drive. They have no cou-
pler or bearing assembly. These pumps do not require
lubrication. Others require SAE-30 non-detergent oil to
lubricate  both  the  motor  and  the  bearing  assembly.
Check pump motor for type before adding oil.
Clean dust and lint from pump and motor. Check pump
coupler and tighten if necessary.
Flush  system  before  putting  into  operation  to  ensure
that foreign material does not damage pump seals.
CAUTION: Propane  gas  is  heavier  than  air  and
sinks to the ground. Exercise extreme care in light-
ing heater in confined areas.
CAUTION: Pump must be off to check oil in bearing
assembly. Do not run pump without water in system.