Raypak 1334001 Manuel D’Utilisation

Page de 52
6
RECEIVING EQUIPMENT
On receipt of the equipment, visually check for exter-
nal damage to the carton or the shipping crate. If the
carton or shipping crate is damaged, make a note on
the Bill of Lading and report the damage to the Carrier
immediately. Remove the heater from the carton or the
shipping crate.
Do NOT use the shipping crate base as an installation
base. On occasion, items are shipped loose. Be sure
that you receive the number of packages indicated on
the Bill of Lading.
When  ordering  parts,  you  must  specify  Model  and
Serial  Number  of  the  heater.  When  ordering  under
warranty  conditions,  you  must  also  specify  date  of
installation.
Raypak  recommends  that  this  manual  be  reviewed
thoroughly  before  installing  your  Raypak  heater.  If
there  are  any  questions  which  this  manual  does  not
answer,  please  contact  the  factory  or  your  local
Raypak representative.
Claims for shortages and damages must be filed with
carrier by consignee. Permission to return goods must
be  factory-authorized  and  are  subject  to  a  stocking
charge.
Purchased  parts  are  subject  to  replacement  only
under  the  manufacturer's  warranty.  Debits  for  defec-
tive replacement parts will not be accepted and will be
replaced in kind only per our standard warranties.
Model Identification
The model identification number and the heater serial
number are found on the heater data plate. The model
number  will  have  the  form  WH1-0514A  or  similar
depending  on  the  heater  model.  (WH  =  Hot  Water
Supply  System,  1  =  on/off  firing,  0514  =  size  of
heater).
Rated inputs are suitable for up to 2000 feet elevation.
For  elevations  above  2000  feet,  reduce  input  4%  for
each 1000 feet above sea level.
Time/Temperature
Relationships in Scalds
The  temperature  of  the  water  in  the  storage  tank
heater  can  be  regulated  by  setting  the  temperature
dial on front of the tankstat. To comply with safety reg-
ulations,  the  tankstat  was  set  at  its  lowest  setting
before shipment from the factory. 
Fig. 1 illustrates a mechanical tankstat. To adjust the
water temperature, insert a small straight screwdriver
into slotted screw in hole in front of tankstat and turn
wheel to desired setting. Thermostat is adjustable up
to 190°F.
Fig. 1: Tankstat Adjustment
DANGER: There is a Hot Water SCALD Potential if
the tankstat is set too high.
CAUTION: Hotter  water  increases  the  risk  of
SCALDING!
NOTE: When  this  heater  is  supplying  general
purpose  hot  water  requirements  for  use  by
individuals,  a  thermostatically  controlled  mixing
valve for reducing point of use water temperature is
recommended  to  reduce  the  risk  of  scald  injury.
Contact  a  licensed  plumber  or  the  local  plumbing
authority for further information.
WARNING: Pump  motors  should  NOT  be
supported  by  any  type  of  stand  or  support  from
above  due  to  possible  misalignment  of  pump  and
motor which might occur.