Figure 10 shows typical attachment of water piping to water heater. The  
water heater is equipped with 3/4 inch NPT water connections.
note: If using copper tubing, solder tubing to an adapter before 
attaching the adapter to the water heater connections.  do not 
solder the water lines directly to the water heater connections.  
It will harm the dip tube and damage the tank.
t & p valve and pipe Insulation (if supplied)
Remove insulation for T & P valve and pipe connections from carton.
fIGure 11.
Fit pipe insulation over the incoming cold water line and the hot water 
line. Make sure that the insulation is against the top cover of the heater.
Fit T & P valve insulation over valve. Make sure that the insulation 
does not interfere with the lever of the T & P valve.
Secure all insulation using tape.
teMperature-pressure relIef valve
Explosion Hazard
Temperature-Pressure Relief Valve
must comply with ANSI Z21.22-
CSA 4.4 and ASME code.
Properly sized temperature-
pressure relief valve must be
installed in opening provided.
Can result in overheating and
excessive tank pressure.
Can cause serious injury or death.
This water heater is provided with a properly rated/sized and certified 
combination  Temperature-Pressure  Relief  Valve  (T&P  valve)  by 
the manufacturer. The valve is certified by a nationally recognized 
testing laboratory that maintains periodic inspection of production of 
listed equipment of materials as meeting the requirements for Relief 
Valves for Hot Water Supply Systems, ANSI Z21.22 • CSA 4.4, and 
the code requirements of ASME.
If replaced, the new T&P valve must meet the requirements of local 
codes, but not less than a combination Temperature-Pressure Relief 
Valve rated/sized and certified as indicated in the above paragraph. The 
new valve must be marked with a maximum set pressure not to exceed 
the marked hydrostatic working pressure of the water heater (150 psi = 
1,035 kPa) and a discharge capacity not less than the water heater Btu/
hr or kW input rate as shown on the water heater’s model rating label.
note:  In  addition  to  the  factory  installed  Temperature-Pressure 
Relief Valve on the water heater, each remote storage tank that may 
be installed and piped to a water heating appliance must also have its 
own properly sized, rated and approved Temperature-Pressure Relief 
Valve  installed.  Call  the  toll  free  technical  support  phone  number 
listed on the back cover of this manual for technical assistance in 
sizing a Temperature-Pressure Relief Valve for remote storage tanks.
For  safe  operation  of  the  water  heater,  the  Temperature-Pressure 
Relief Valve must not be removed from its designated opening nor 
plugged. The Temperature-Pressure Relief Valve must be installed 
directly into the fitting of the water heater designed for the relief valve. 
Install discharge piping so that any discharge will exit the pipe within 
6 inches (15.2 cm) above an adequate floor drain, or external to the 
building. In cold climates it is recommended that it be terminated at 
an adequate drain inside the building. Be certain that no contact is 
made with any live electrical part. The discharge opening must not 
be blocked or reduced in size under any circumstances. Excessive 
length, over 30 feet (9.14 m), or use of more than four elbows can 
cause restriction and reduce the discharge capacity of the valve.
No valve or other obstruction is to be placed between the Temperature-
Pressure Relief Valve and the tank. Do not connect discharge piping 
directly to the drain unless a 6” (15.2 cm) air gap is provided. To prevent 
bodily injury, hazard to life, or property damage, the relief valve must be 
allowed to discharge water in adequate quantities should circumstances 
demand.  If  the  discharge  pipe  is  not  connected  to  a  drain  or  other 
suitable means, the water flow may cause property damage.
Water Damage Hazard
Temperature-Pressure Relief Valve discharge
pipe must terminate at adequate drain.
CAUTION
t&p valve discharge pipe requirements:
•  Shall not be smaller in size than the outlet pipe size of the valve, 
or have any reducing couplings or other restrictions.
•  Shall not be plugged or blocked.
•  Shall not be exposed to freezing temperatures.
•  Shall be of material listed for hot water distribution.
•  Shall be installed so as to allow complete drainage of both the 
Temperature-Pressure Relief Valve and the discharge pipe.
•  Must terminate a maximum of six inches above a floor drain or 
external to the building. In cold climates, it is recommended that 
the  discharge  pipe  be  terminated  at  an  adequate  drain  inside 
the building.
•  Shall not have any valve or other obstruction between the relief 
valve and the drain.
Burn hazard.
Hot water discharge.
Keep clear of Temperature-
Pressure Relief Valve
discharge outlet.
The Temperature-Pressure Relief Valve must be manually operated 
at least twice a year. Caution should be taken to ensure that (1) no 
one is in front of or around the outlet of the Temperature-Pressure 
Relief Valve discharge line, and (2) the water manually discharged 
will  not  cause  any  bodily  injury  or  property  damage  because  the 
water may be extremely hot. If after manually operating the valve, it 
fails to completely reset and continues to release water, immediately 
close  the  cold  water  inlet  to  the  water  heater,  follow  the  draining 
instructions in this manual, and replace the Temperature-Pressure 
Relief Valve with a properly rated/sized new one.
note: The purpose of a Temperature-Pressure Relief Valve is to 
prevent excessive temperatures and pressures in the storage tank. 
The  T&P  valve  is  not  intended  for  the  constant  relief  of  thermal 
expansion. A properly sized thermal expansion tank must be installed 
on  all  closed  systems  to  control  thermal  expansion,  see  Closed 
Water Systems and Thermal Expansion on page 12.
If  you  do  not  understand  these  instructions  or  have  any  questions 
regarding  the  Temperature-Pressure  Relief  Valve  call  the  toll  free 
number listed on the back cover of this manual for technical assistance.