State Industries SBD85500PE Manuel D’Utilisation

Page de 52
12
water temperature control and mixing ValVes
Water temperature over 125°F (52°C)
can cause severe burns instantly
resulting in severe injury or death.
Children, the elderly and the
physically or mentally disabled are at
highest risk for scald injury.
Feel water before bathing or
showering.
Temperature limiting devices such as
mixing valves must be installed
when required by codes and to
ensure safe temperatures at fixtures.
Water  heated  to  a  temperature  which  will  satisfy  clothes 
washing, dish washing, and other sanitizing needs can scald 
and  cause  permanent  injury  upon  contact.  Short  repeated 
heating  cycles  caused  by  small  hot  water  uses  can  cause 
temperatures at the point of use to exceed the water heater’s 
temperature setting by up to 20°F (11°C).
some people are more likely to be permanently injured by 
hot water than others. These include the elderly, children, the 
infirm and the physically/mentally disabled. Table 6 shows the 
approximate time-to-burn relationship for normal adult skin. If 
anyone using hot water provided by the water heater being 
installed fits into one of these groups or if there is a local code 
or state law requiring a certain water temperature at the point 
of use, then special precautions must be taken.
In addition to using the lowest possible temperature setting 
that  satisfies  the  demand  of  the  application  a  Mixing  Valve 
should be installed at the water heater (see Figure 10) or at 
the hot water taps to further reduce system water temperature.
Mixing  valves  are  available  at  plumbing  supply  stores. 
Consult a Qualified Installer or Service Agency. Follow mixing 
valve manufacturer’s instructions for installation of the valves.
taBle 6.
Water Temperature
Time to Produce 2nd & 3rd
Degree Burns on Adult skin
180°F (82°C)
Nearly instantaneous
170°F (77°C)
Nearly instantaneous
160°F (71°C)
About 1/2 second
150°F (66°C)
About 1-1/2 seconds
140°F (60°C)
Less than 5 seconds
130°F (54°C)
About 30 seconds
120°F (49°C)
More than 5 minutes
gas pressure reQuirements
Natural gas models require a minimum gas supply pressure of 
4.5” W.C. Propane gas models require a minimum gas supply 
pressure of 11" W.C. The minimum supply pressure is measured 
while gas is not flowing (static pressure) AND while gas is flowing 
(dynamic  pressure). The  supply  pressure  (static  and  dynamic) 
should never fall below the specified minimum supply pressure. 
The  supply  pressure  should  be  measured  with  all  gas  fired 
appliances connected to the common main firing at full capacity. 
If the supply pressure drops more than 1.5” W.C. as gas begins 
to flow to the water heater then the supply gas system including 
the  gas  line  and/or  the  gas  regulator  may  be  restricted  or 
undersized. See Supply Gas Regulator section and Gas Piping 
section of this manual.
The gas valve on all models has a maximum gas supply 
pressure  limit  of  14"  W.C.  The  maximum  supply  pressure  is 
measured while gas is not flowing (static pressure) AND while 
gas is flowing (dynamic pressure).
supply gas regulator
The  water  heater  covered  by  this  manual  may  require 
the  installation  of  a  supply  gas  regulator.  If  the  supply  gas 
pressure exceeds 14 inches W.C. a supply gas regulator must 
be  used.  If  the  gas  supply  pressure  exceeds  14"  W.C.  in  a 
multiple  water  heater  installation,  each  water  heater  must 
have its own supply gas regulator. If required, the supply gas 
regulator shall be rated at or above the Btu/hr input rating of 
the water heater it supplies.
Supply gas regulators shall have inlet and outlet connections 
not less than the minimum supply gas line size for the water 
heater they serve as shown in Table 9. The Maxitrol 325-7L or 
equivalent is recommended.
power supply
The  water  heaters  covered  in  this  manual  require  a  120 
VAC,  1Ø  (single  phase),  60Hz,  15  amp  power  supply  and 
must also be electrically grounded in accordance with local 
codes or, in the absence of local codes, with the National 
Electrical Code, ANSI/NFPA 70 or the Canadian Electrical 
Code, CSA C22.1.
installation reQuirements