State Industries A B C D E F 100 Manuel D’Utilisation

Page de 44
11
in an alcove or closet, the entire floor must be covered by the panel.
Failure to heed this warning may result in a fire hazard.
Minimum  clearances  between  the  water  heater  and  combustible 
construction are 0 inch at the sides and rear, 5.5” (14.0 cm) from the front
and 12” (30.5 cm) from the top. (Standard clearance.) If clearances
stated  on  the  heater  differ  from  standard  clearances,  install  water 
heater according to clearances stated on the heater.
Adequate clearance 24” (61.0 cm) for servicing this appliance should be
considered before installation, such as changing the anodes, etc.
A minimum clearance of 5.5” (14.0 cm) must be allowed for access to
replaceable parts such as the thermostats, drain valve and relief valve.
When  installing  the  heater,  consideration  must  be  given  to  proper
location. Location selected should be as close to the wall as practicable
and as centralized with the water piping system as possible.
FIGURE 4.
InsulatIon BlanKets
Insulation blankets are available to the general public for external use
on gas water heaters but are not necessary with these products. The
purpose of an insulation blanket is to reduce the standby heat loss
encountered with storage tank heaters. Your water heater meets or
exceeds the Energy Policy Act standards with respect to insulation and
standby loss requirements, making an insulation blanket unnecessary.
Should you choose to apply an insulation blanket to this heater, you
should  follow  these  instructions  (For  identification  of  components
mentioned below, see Figure 1). Failure to follow these instructions
can restrict the air flow required for proper combustion, potentially
resulting in fire, asphyxiation, serious personal injury or death.
•  Do not apply insulation to the top of the water heater, as this will  
interfere with safe operation of the blower assembly.
•  Do not cover the outer door, thermostat or temperature & pressure  
relief valve.
•  Do not allow insulation to come within 2” (5.1 cm) of the floor to  
prevent blockage of combustion air flow to the burner.
•  Do not cover the instruction manual. Keep it on the side of the  
water heater or nearby for future reference.
•  Do obtain new warning and instruction labels from the manufacturer  
for placement on the blanket directly over the existing labels.
•  Do  inspect  the  insulation  blanket  frequently  to  make  certain  it  
does not sag, thereby obstructing combustion air flow.
coMBustIon aIr and ventIlatIon
A gas water heater cannot operate properly without the correct amount
of air for combustion. Do not install in a confined area such as a closet,
unless  you  provide  air  as  shown  in  the  “Facts  to  Consider About
Location” section. Never obstruct the flow of ventilation air. If you have
any doubts or questions at all, call your gas supplier. Failure to provide
the proper amount of combustion air can result in a fire or explosion
and cause death, serious bodily injury, or property damage.
FIGURE 5.
If this water heater will be used in beauty shops, barber shops, cleaning
establishments, or self-service laundries with dry cleaning equipment,
it is imperative that the water heater (s) be installed direct vent so that
all air for combustion and ventilation is taken from outdoors.
  
Propellants  of  aerosol  sprays  and  volatile  compounds,  (cleaners,
chlorine based chemicals, refrigerants, etc.) in addition to being highly
flammable in many cases, will also react to form corrosive hydrochloric
acid when exposed to the combustion products of the water heater.
The results can be hazardous, and also cause product failure.
applIances In unconfIned spaces
unconfIned  space  is  space  whose  volume  is  not  less  than  
50 cubic feet per 1,000 Btu per hour (4.8 cubic meters per kW) of the
aggregate input rating of all appliances installed in that space. Rooms
communicating directly with the space in which the appliances are
installed, through openings not furnished with doors, are considered
a part of the unconfined space.
In  unconfined  spaces  in  buildings,  infiltration  may  be  adequate  to
provide  air  for  combustion,  ventilation  and  dilution  of  flue  gases.
However,  in  buildings  of  tight  construction  (for  example,  weather
stripping, heavily insulated, caulked, vapor barrier, etc.), additional air
may need to be provided using the methods described in “Appliances
in Confined Space” that follows.”
applIances In confIned spaces
confIned space is a space whose volume is less than 50 cubic
feet per 1,000 Btu per hour (4.8 cm per kW) of the aggregate input
rating of all appliances installed in that space.
When drawing combustion air from inside a conventionally constructed
building to a confined space, such a space shall be provided with
two permanent openings. ONE WITHIN 12 INCHES (30 cm) OF 
THE  ENCLOSURE  TOP AND  ONE  WITHIN  12  INCHES  (30
cm) OF THE ENCLOSURE BOTTOM. Each opening shall have