State Industries A B C D E F 100 Manuel D’Utilisation

Page de 44
14
Figures 2 and 10 show the typical attachment of the water piping to
the water heater. The water heater is equipped with 3/4 inch NPT
water connections.
note: If using copper tubing, solder tubing to an adapter 
before attaching the adapter to the water heater connections.  
do  not  solder  the  water  lines  directly  to  the  water  heater 
connections.    It  will  harm  the  dip  tube  and  damage  the 
tank.
T & P Valve and Pipe Insulation (if supplied)
Remove  insulation  for  T  &  P  valve  and  pipe  connections  from
carton.
FIGURE 11.
Fit  pipe  insulation  over  the  incoming  cold  water  line  and  the
hot water line. Make sure that the insulation is against the top
cover of the heater.Fit T & P valve insulation over valve. Make
sure that the insulation does not interfere with the lever of the 
T & P valve.
Secure all insulation using tape.
teMperature-pressure relIef valve
This  heater  is  provided  with  a  properly  certified  combination  
temperature - pressure relief valve by the manufacturer.
The valve is certified by a nationally recognized testing laboratory
that maintains periodic inspection of production of listed equipment of
materials as meeting the requirements for Relief Valves for Hot Water
Supply Systems, ANSI Z21.22 • CSA 4.4, and the code requirements
of ASME.
If replaced, the valve must meet the requirements of local codes, but
not less than a combination temperature and pressure relief valve
certified as indicated in the above paragraph.
The  valve  must  be  marked  with  a  maximum  set  pressure  not  to
exceed the marked hydrostatic working pressure of the water heater 
(150 psi = 1,035 kPa) and a discharge capacity not less than the
water  heater  Btu/hr  input  rate  as  shown  on  the  water  heater’s
model rating plate.
For safe operation of the water heater, the relief valve must not be
removed from its designated opening nor plugged.
The temperature-pressure relief valve must be installed directly into
the fitting of the water heater designed for the relief valve. Position
the valve downward and provide tubing so that any discharge will
exit only within 6 inches (15.2 cm) above, or at any distance below
the structural floor.  Be certain that no contact is made with any 
live electrical part. The discharge opening must not be blocked
or reduced in size under any circumstances. Excessive length,
over 30 feet (9.14 m), or use of more than four elbows can cause
restriction  and  reduce  the  discharge  capacity  of  the  valve,  see
Figures 10.
No valve or other obstruction is to be placed between the relief
valve and the tank. Do not connect tubing directly to discharge
drain unless a 6” (15.2 cm) air gap is provided. To prevent bodily
injury, hazard to life, or property damage, the relief valve must
be allowed to discharge water in quantities should circumstances
demand. If the discharge pipe is not connected to a drain or other
suitable means, the water flow may cause property damage.
The Discharge Pipe:
• Shall not be smaller in size than the outlet pipe size of the valve, or  
have any reducing couplings or other restrictions.
• Shall not be plugged or blocked.
• Shall be of material listed for hot water distribution.
• Shall be installed so as to allow complete drainage of both the  
temperature-pressure relief valve, and the discharge pipe.
• Shall terminate at an adequate drain.
• Shall not have any valve between the relief valve and tank.