Rinnai R50LSI Manuel D’Utilisation

Page de 44
 
26 
VA Series Indoor LS Manual 
•  Vertical terminations must incorporate a condensate 
drain and trap as close as possible to the appliance. 
•  Slope any horizontal venting 1/4 inch per foot (19 
mm / m), towards the heater if the condensate 
collector is used, or towards the exhaust terminal if 
the condensate collector is not used. 
•  Dispose of condensate per local codes. 
•  The condensate trap must contain a minimum of 3 
inches (75 mm) of water. 
•  Rinnai LSi tankless water heaters have an 
integrated condensate collector. 
•  Rinnai offers a condensate trap.   
•  Regions of cold climate will create more condensate 
in the vent system.  The condensate collector 
should be used in cold climates. 
  Venting 
Instructions      
                       
•  This water heater is a direct vent water heater and 
therefore is certified and listed with the vent 
system.  You must use vent components that are 
certified and listed with the water heater model. 
•  Do not combine vent components from different 
manufacturers. 
•  The vent system must vent directly to the outside 
of the building and use outside air for combustion. 
•  Every vent connection must be accessible for 
inspection, cleaning, and replacement. 
•  Venting should be as direct as possible with a 
minimum number of pipe fittings. 
•  Avoid dips or sags in horizontal vent runs by 
installing supports per the vent manufacturer’s 
instructions. 
•  Support horizontal vent runs every four feet and all 
vertical vent runs every six feet or in accordance 
with local codes. 
•  Vent diameter must not be reduced. 
•  Do not connect the venting system with an existing 
vent or chimney. 
•  Do not common vent with the vent pipe of any 
other water heater or appliance. 
•  Vent connections must be firmly pressed together 
so that the gaskets form an air tight seal. 
•  R50LSi, R75LSi, R94LSi:  The vent piece 
connected to the water heater must be secured 
with one self-tapping screw. 
•  Refer to the instructions of the vent system 
manufacturer for component assembly instructions. 
Condensate  
Condensate formation can occur in high efficiency 
direct vent appliances.  To prevent condensate 
damage follow these instructions. 
Intake / Exhaust Guidelines 
Refer to the specific instructions on your vent product for additional installation requirements. 
NOTICE 
Provisions must be made to prevent the condensate 
from entering the water heater.  Without proper 
drainage or disposal, condensate will damage the heat 
exchanger. 
     WARNING 
If the condensate collector is not used, the drain pipe 
must be capped to prevent exhaust gases and 
condensate from entering the building.  The cap is 
supplied on the appliance.