Installation & Service Manual
TM
Requirements for installation in 
Canada
1.  Installations must be made with a vent pipe system 
 
certified to ULC-S636.
2.  The first three (3) feet of plastic vent pipe from the 
 
appliance flue outlet must be readily accessible for visual 
 inspection.
3.  The components of the certified vent system must not be 
 
interchanged with other vent systems or unlisted 
 
pipe/fittings.  For concentric vent installations, the inner 
 
vent tube must be replaced with field supplied certified vent 
 
material to comply with this requirement.
4.  The 3" Concentric Vent Kit available from Lochinvar (see 
 
Section 3 – Sidewall Termination – Optional Concentric 
 Vent) and the 3" Concentric Vent Kit available from IPEX 
 
are both approved for use on the Shield water heater.  Both 
 
kits are listed to the ULC-S636 standard for use in Canada.
Minimum / Maximum allowable 
combustion air and vent piping lengths 
are as follows:
Combustion Air = 12 equivalent feet minimum / 100 
equivalent feet maximum
Vent = 12 equivalent feet minimum / 100 equivalent feet 
maximum
When determining equivalent combustion air and vent 
length, add 5 feet for each 90° elbow and 3 feet for each 45° 
elbow. 
EXAMPLE:  20 feet of PVC pipe + (4) 90° elbows + (2) 45° 
elbows + (1) concentric vent kit (CVK3003) = 49 equivalent 
feet of piping.
The appliance output rating will reduce 
by up to 1.5% for each 25 feet of vent 
length.
 NOTICE
Table 2B Concentric Vent Kit Equivalent Vent Lengths
Sizing
The Shield water heater uses model specific combustion air 
intake and vent piping sizes as detailed in Table 2A below.
Table 2A Air Intake/Vent Piping Sizes
 NOTICE
Model
Air Intake
Vent
SNR150-100 -- SNR200-100
3 inches
3 inches
SNA285-125 -- SNA500-125
4 inches
4 inches
Model
Kit 
Number
Equivalent 
Vent Length
SNR150-100 -- SNR200-100 CVK3003
3 feet
SNA285-125
CVK3007
3 feet
SNA400-125
CVK3007
5 feet
SNA500-125
CVK3007
30 feet
Increasing or decreasing combustion air 
or vent piping sizes is not authorized.