Honeywell TB8575 Manuel D’Utilisation

Page de 20
TB6575/TB8575 DIGITAL FAN COIL THERMOSTATS
62-0311—13
2
SPECIFICATIONS
Supply Voltages:
TB6575A1016 and TB6575B1000:
• 120 Vac ±10% at 50/60Hz
• 240 Vac -15% to +10% at 50/60Hz
TB6575C1016:
• 120 Vac ±10% at 50/60Hz
• 240 Vac -15% to +10% at 50/60Hz
• 277 Vac ±10% at 50/60Hz
TB8575A1016:
• 20 to 30 Vac at 50/60Hz (using 24 Vac, Class 2, 
NEMA rated transformer)
Safety Fuse:  15 A, 350V. If the safety fuse blows, the 
thermostat must be replaced. The fuse is not field 
replaceable.
Electrical Ratings:  (see Table 1).
Environmental Ratings:
Temperature:
Operating Range: 18°C to 49°C (0°F to 120°F).
Shipping and Storage Range: -29°C to 49°C (-20°F to 
120°F). 
Humidity: 5% to 90% RH, non-condensing.
Onboard Temperature Sensor: 
Type: 10K NTC
Working Range: 18°C to 49°C (0°F to 120°F)
Display Range: 0°C to 37°C (32°F to 99°F)
Accuracy ±2.0°F at 70°F
Remote Temperature Sensor (optional):
Type: 20K NTC
Working Range: 18°C to 49°C (0°F to 120°F)
Display Range: 0°C to 37°C (32°F to 99°F)
Accuracy ±2.0°F at 70°F
Remote Pipe Sensor (optional):
Type: 20K NTC
Working Range: 0°C to 93°C (32°F to 199°F)
Display Range: 0°C to 93°C (32°F to 199°F)
Accuracy ±5.0°F over the temperature sensing range
Remote Setback Input: Dry contact, maximum 
resistance of 100 ohms. TB6575 – 9Vdc, < 4 mA; TB8575 
– 16 Vdc, < 5 mA. Note Electrical WARNING on page 3.
Remote Setback Range:
Heating: 10°C to 21°C (50°F to 70°F).
Cooling: 22°C to 32°C (72°F to 90°F).
Enclosure: Plastic (cover, sub-base, and optional adap-
tor plate) 
Junction Box Mounting: Direct mounting on a horizontal 
single gang NEMA 2 x 4 in. surface mount electrical box, 
or on 4 x 4 in. box or vertical 2 x 4 in. surface mount 
electrical box with the optional 50033847-001 adapter 
plate.
Dimensions: See Fig. 1 on page 3.
Wiring: 11 screw-in terminals located on the sub-base 
capable of accepting up to 2 x 18 AWG (0.8 sq. mm), 1 x 
16 AWG (1.3 sq. mm), or 1 x 14 AWG (2.1 sq. mm) wires. 
Accepts stranded or unstranded 14-28 gauge wire.
NOTES:
1. The TB6575A1016 and TB6575C1016 models 
are pre-fitted with color-coded fly leads (16 
AWG) attached to seven terminals.
2. The TB6575B1000 model is pre-fitted with color-
coded fly leads (16 AWG) attached to six 
terminals.
3. The TB8575A1016 model does not have fly 
leads attached to any terminals. 
4. See Table 3 on page 5 for fly lead usage.
Minimum Operational Life (at maximum load):
Thermostat contacts: 100,000 cycles
Approvals:
CSA Certified C/US for Canada and the U.S.A. Meets 
the same requirements as UL-873 and UL 1/4 HP.
FCC Part 15 Class B
Accessories:
• 50033847-001 – Adapter plate for mounting on a 
vertical 2 x 4 in. single-gang or double-gang NEMA 
standard vertical switch box (6 1/4 in. (158 mm) x 5 1/
16 in. (128 mm) x 13/22 in. (10 mm)).
• TR21 – 20K Ohm NTC Non-Linear Remote 
temperature sensor.
Other acceptable remote temperature sensors are —
• 20K Ohm: C7041B2005, C7041B2013, 
C7041C2003, C7041P2004, C7770A1006, 
C7772A1004, and C7772A1012
• 10K Ohm (for averaging only): TR21-A
• PS20 (535-34AB08-203) – Remote pipe sensor 
(20K Ohm)
• W6380B1005 – Fan Coil Unit Relay Control Center
• WSK-24 - Wireless Occupancy Solution (Receiver, 
occupancy sensor and door sensor)
Models, applications, and features:
Table 2 identifies the applications and features of each 
model.
Table 1. Electrical Ratings.
Component
Amps (inductive) for:
24 Vac 120 Vac 240 Vac 277 Vac
Fan Relay
1.0 A
6.0 A
3.0 A
2.4 A
Heat/Cool Relay
1.0 A
1.0 A
1.0 A
1.0 A