INSTALLER/CONFIGURATION MENU 
To enter the Configuration Menu, SYSTEM must be set to 
HEATCOOLEMER or AUTO. With thermostat in Heat, Cool or 
Auto, in normal operation, press the Menu button for at least 5 seconds. The display will show item #1 in the table below. Press 
Menu to advance to the next menu, Press 
 or 
 to change an item option. Shaded items are not available to 1F83.
INSTALLER/CONFIGURATION MENU        
MENU 
SCREEN #
HP
MS/
SS
DISPLAYED
(FACTORY DEFAULT)
Press 
 or 
 to
select from listed options
COMMENTS
1F85 1F83
01
01  
(OFF) Lk
L
Selects Keypad Lockout. 
(Not available on earlier models, see 37-6894D)
02
02  
(000) Lk
001  to 999
Selects Keypad lockout combination number 
03
03  
(MS 2)
HP 1, SS 1
Selects Multi-Stage (MS 2 No Heat Pump),
Heat Pump 1 (HP 1, 1 compressor),
or Single Stage (SS 1)
04
04
(GAS)
ELE
Select Gas or Electric heat
(ELE)
GAS
05
05  
(0) 
CS
1, 2, 4, 5, 6
Selects Cool Savings
Value 1 (low) to 6 (high), Value 0 Disables Feature
06
—  
(On) 
E
OFF
Selects Energy Management Recovery (EMR)
On or OFF. 
1F85 only
07
06
(ME) 
CR Heat
SL, FA
Adjustable Anticipation:
Selects heating cycle rate for MS or SS
08
07  
(ME) 
CR Cool
SL, FA
Adjustable Anticipation: Selects the cycle rate for 
cooling (only when MS2 or SS1 is selected in item 1) 
09
08  
(ME)
CR Heat Pump
SL, FA
Adjustable Anticipation (Heat Pump) 
(only when heat pump is selected in #1)
10
09  
(FA)
CR Emer
SL
Selects the cycle rate for Emergency mode and 
Auxiliary stage if Heat Pump is selected in item 1)
11
10  
(OFF) CL
CL On
Compressor Lockout Time
12
11  
Heat-Auto-Cool-Off
Auto-Off, Cool-Off,
Heat-Off without Fan,
Heat-Off Heat-Cool-Off
Selects System Mode Configuration
13
12  
(On) dL
dL OFF
Selects Display Light On or OFF
14
13  
0
(current temperature)
1 HI, 2 HI, 3 HI, 4 HI,
1 LO, 2 LO, 3 LO, 4 LO
Adjustable Ambient Temperature Display
15
14  
°
F
°
C
Selects Fahrenheit/Celsius Temperature Display
16
15  
L (90) Heat
L 62 to L 89
Selects Limited HEAT Range
17
16  
L (45) Cool
L 46 to L 82
Selects Limited COOL Range
18
—   
P3
P0, P2
Defaults for 5+1+1 programming (P3) but non-
programmable (PO) or 5+2 programming (P2)
is available on most models. 
1F85 only
19
—  
(On) AS Heat
OFF
Automatic Schedule for heat mode. 
1F85 only. 
NA to Cool only system.
20
—  
(On) AS Cool
OFF
Automatic Schedule for cool mode. 
1F85 only. 
NA to Heat only system.
21
17
(On) FA Heat
OFF
Fast Heat option may be disabled by selecting OFF. 
NA to SS config. NA to Cool only system.
22
18
(On) FA Cool
OFF
Fast Cool option may be disabled by
selecting OFF. NA to SS config. 
NA to Heat only system.
23
19  
(OFF) CA
On
Selects active Comfort Alert On or OFF.
Require CA II Module. (Not available on earlier models)
24
—  
(On) dS
OFF
Selects Automatic 
daylight Savings Time option
On or OFF. 
1F85 only
25
20   (OFF) Change Filter
On
Selects Filter Change-out Indicator On or OFF.
26
21   (200 h) Change Filter
25-1975 h
Change Filter time in 25 hour increments. This
menu only appears if On is selected in above.
27
22  
(o) On Cool
(b) On Heat
Selects operation of the reversing valve terminal 
(O/B) output as an O or B terminal.