Empire Comfort Systems DVP42FP7 Manuel D’Utilisation

Page de 52
Page 8
17375-6-0705
Figure 6 
T
he gas pipeline can be brought in through the right or left side of 
the appliance. Consult the current National Fuel Gas Code, ANSI 
Z223.1 CAN/CGA-B149 (.1 or .2) installation code.
GAS SUPPLY
Installing a New Main Gas Cock
Each appliance should have its own manual gas cock.
In  the  state  of  Massachusetts  the  gas  cock  must  be  a T  handle 
type.
A manual main gas cock should be located in the vicinity of the 
unit. Where none exists, or where its size or location is not ad-
equate, contact your local authorized installer for installation or 
relocation.
Compounds used on threaded joints of gas piping shall be resistant 
to the action of liquefied petroleum gases. The gas lines must be 
checked for leaks by the installer. This should be done with a soap 
solution watching for bubbles on all exposed connections, and if 
unexposed, a pressure test should be made. 
Never use an exposed flame to check for leaks. Appliance must 
be disconnected from piping at inlet of control valve and pipe 
capped or plugged for pressure test. Never pressure test with 
appliance connected; control valve will sustain damage!
NOTE: 
The millivolt gas controls are equipped with a captured 
screw type pressure test point, therefore it is not necessary to provide 
a 1/8" test point up stream of the control.
On direct ignition valves, hex plugs may be replaced with hose fittings 
for pressure checks, then reinstalled before operating fireplace.
When using copper or flex connector use only approved fittings. 
The appliance and it’s individual shut off valve must be disconnected 
from supply piping system during any pressure testing of that system 
at test pressures in excess of 1/2 psig (3.5kPa).
The appliance must be isolated from the gas supply piping system 
by closing its individual manual shut off valve during any pressure 
testing of the gas supply piping system at test pressures equal to or 
less than 1/2 psig (3.5kPa).
Attention! If one of the procedures results in pressures in excess 
of 1/2 psig (14" w.c.) (3.5 kPa) on the fireplace gas valve, it will 
result in a hazardous condition.
Checking Manifold Pressures
Both  Propane  and  Natural  gas  valves  have  a  built-in  pressure 
regulator in the gas valve. Natural gas models will have a manifold 
pressure of approximately 3.5" w.c. (.871kPa) at the valve outlet 
with the inlet pressure to the valve from a minimum of 4.5" w.c. 
(1.120kPa) for the purpose of input adjustment to a maximum of 
10.5" w.c. (2.615kPa). Propane gas models will have a manifold 
pressure approximately 10.0" w.c. 
(2.49kPa) at the valve outlet with 
the  inlet  pressure  to  the  valve 
from  a  minimum  of  11.0"  w.c. 
(2.739kPa) for the purpose of input 
adjustment to a maximum of 13.0" 
w.c. (3.237kPa). 
Figure 7 
Gas Supply Pressure (inches w.c.)
Minimum
Normal
Maximum
Natural Gas
4.5"
7.0"
*14.0"
LP (Propane)
10.8"
11.0"
*14.0"
Manifold Pressure (inches w.c.)
Normal (HI)
Natural Gas
3.5"
LP (Propane)
10.0"
Note: Never use plastic pipe. Check to confirm whether your 
local codes allow copper tubing or galvanized.
Note: Since some municipalities have additional local codes, it is 
always best to consult your local authority and installation code.
The use of the following gas connectors is recommended:
—  ANS  Z21.24  Appliance  Connectors  of  Corrugated  Metal 
Tubing and Fittings.
—  ANS Z21.45 Assembled Flexible Appliance Connectors of 
Other Than All-Metal Construction
The above connectors may be used if acceptable by the authority 
having  jurisdiction. The  state  of  Massachusetts  requires  that  a 
flexible appliance connector cannot exceed three feet in length.
Recommended Gas Pipe Diameter
Pipe Length
(Feet)
Schedule 40 Pipe 
Inside Diameter
Tubing, Type L
Outside Diameter
Nat.
L.P.
Nat.
L.P.
0-10
1/2"
12.7mm
3/8"
9.5mm
1/2"
12.7mm
3/8"
9.5mm
11-40
1/2"
12.7mm
1/2"
12.7mm
5/8"
15.9mm
1/2"
12.7mm
41-100
1/2"
12.7mm
1/2"
12.7mm
3/4"
19mm
1/2"
12.7mm
101-150
3/4"
19mm
1/2"
12.7mm
7/8"
22.2mm
3/4"
1.9 mm
*NOTE: Remote "RF" Models - 10.5" w.c. maximum