Empire Comfort Systems DVP48FP9 Manuel D’Utilisation

Page de 52
Page 7
17375-6-0705
Mantel Chart (Figure 3)
Figure 3
Clearances (Figure 4)
Clearance from top front edge of fireplace to ceiling is 36"
Clearance from side of fireplace to adjacent sidewall is 6".
(914mm)
Figure 4
LOCATING FIREPLACE
Figure 5
Note:  Island (C) and Room Divider 
(D) installation is possible as long 
as  the  horizontal  portion  of  the 
vent system (H) does not exceed 
20 feet with a minimum vertical 
run of 8 feet. See details in Venting 
Section.
When you install your Direct Vent 
Fireplace in (D) Room divider or 
(E) Flat on wall corner positions, 
a minimum of 6 inches clearance 
must  be  maintained  from  the 
perpendicular  wall  and  the  front 
edge of the appliance.
CLEARANCES
Figure 2
Combustible Material
No greeting cards, stockings or ornamentation of any type should 
be placed on or attached to the fireplace. The flow of heat can 
ignite combustibles.
CABINET
INSTALLATION
FLUSH WALL
INSTALLATION
ROOM DIVIDER
INSTALLATION
CORNER
INSTALLATION
ANGLED CORNER
INSTALLATION
ISLAND
INSTALLATION
Clearance to Combustibles
Back
0" (0 mm)
Side
0" (0 mm)
Floor
0" (0 mm)
Top Stand-off
0" (0 mm)
Top Framing Edge
3" (76 mm)
SEE MANTLE CHART FOR
MAXIMUM MANTLE DEPTH
NON-COMBUSTIBLE
FIRST 3 (SEE MAGNIFIED
VIEW)
NAILING
FLANGES
GLASS FRONT
TOP FRAMING
LEDGE
FINISHED WALL
(COMBUSTIBLE)
SEE MANTLE CHART
FOR MINIMUM HEIGHT
OF MANTLE ABOVE UNIT
2" x 4" HEADER
STAND OFF
3" (76 mm) HEIGHT
ABOVE TOP OF
FIREPLACE
3"