Emerson Edition 4 Manuel D’Utilisation

Page de 166
Rosemount Tank Radar REX
Chapter 10 Mechanical Installation
10-2
Installation Manual
308014EN, Edition 4
May 2013
10.1.2 Free Space Requirements
There are two flanges available for the Horn Antenna Gauge. One 
inclines the gauge 4° and the other is horizontal. See installation drawing 
for flange dimensions. 
The radar beam is over 30° wide. If the wall intrudes into the 30° radar 
beam when the transmitter is installed with a vertical antenna axis, the 
radar beam has to be directed away from the wall by using the 4° flange. 
This inclination is necessary to ensure maximum accuracy. 
The horizontal flange can be used when the wall does not intrude into the 
30° radar beam. 
For special cases, where maximum accuracy is not required, the 
horizontal flange can be used even when the wall intrudes into the radar 
beam. In doubtful cases, please contact please contact Emerson 
Process Management / Rosemount Tank Gauging or one of its 
representatives for advice. 
Figure 10-2. Free space requirements for RTG with Horn 
antenna.
4
1
3920_FreeSpace_small.eps
Tank wall
Antenna axis
30° radar beam
Vertical plumb line
Vertical plumb line
Vertical plumb line
Vertical plumb line
Antenna axis
Tank wall
30° radar beam