Emerson 1F80-0471 Manuel D’Utilisation

Page de 16
4
INSTALLER/CONFIGURATION MENU 
With thermostat in Heat, Cool or Auto, in normal operation, press the Menu button for at least 5 seconds. The display will 
show item #1 in the table below. Press Menu to advance to the next menu item. Press 
 or 
 to change an item option. 
Shaded items are not available on 1F86.
1)  Select Reversing Valve Output (SS/HP switch must be set 
at HP, omitted if SS/HP switch is SS Position) – The O/B 
option is factory set at "O" position. This will accommodate 
the majority of heat pump applications, which require the 
changeover relay to be energized in COOL. If the thermo-
stat you are replacing or the heat pump being installed 
with this thermostat requires a "B" terminal, to energize the 
changeover relay in HEAT, the O/B option should be set at 
"B" position.
2)  Program Options 1F80 only – This control can be confi gured 
for 5/2 day or 5/1/1 day programming or non-programming 
mode. The default setting is P2, indicating 5/2 day program-
ming. The programs per week can be toggled to P3 or P0 
by pressing the 
 or 
 keys. A selection of 0 Days for 
non-programmable will eliminate the need for EMR, and 
that step in the menu will be skipped.
3)  Select Cool Savings™ and value – Selects the Cool 
Savings feature On or OFF. If selected On, press MENU 
to select the amount of adjustment for the feature in Cool 
mode with 1 (1°) being the least amount of adjustment and 
6 (6°) being the most amount of adjustment. Default value 
is 3 (3°). In normal operation "Saving" will appear under 
"Fan".
 
Cool Savings is an optional energy saving feature that can 
reduce your cooling costs. It is based on the principal that 
lower indoor humidity makes a slightly higher temperature 
feel more comfortable. Cool Savings operates during periods 
of high demand which normally occur on the hottest summer 
days when the cooling system may run for hours to reach 
the thermostat setting. Long cooling run times also lower the 
indoor humidity. Cool Savings very slowly adjusts the setpoint 
temperature to make the setpoint closer to the displayed 
temperature, to a maximum number of degrees selected. 
Adjusting the setpoint temperature over a long cooling run 
time allows the system to reach your set temperature and 
turn off. The room temperature will actually be higher than 
the thermostat displays, but the reduction in humidity will 
allow comfort at the slightly higher temperature. When Cool 
Savings is making adjustments, "Save" will show next to the 
setpoint temperature and the room temperature may vary 
within the adjustment range selected. 
 
If this feature is selected OFF, no change will occur when 
the cooling system is continually running during periods of 
high demand.
INSTALLER/CONFIGURATION MENU
MENU
REF
HP
SS
PRESS 
BUTTON
DISPLAYED
(FACTORY DEFAULT)
Press 
 or 
 to 
select from listed options
COMMENTS
1
1
MENU
On (Cool O)
Heat b On
Reversing Valve Output (SS/HP switch 
must be in the Heat Pump HP position)
2
2
1
MENU
P (2)
P 3, P 0
Selectable Programs Per Week 
(For programmable thermostat only)
3
3
2
MENU Cool Saving CS (OFF)
Cool Saving CS On
Select Cool Savings on or off
MENU
CS (3)
6, 5, 4, 2, 1
Selects Cool Savings value 1 (low) to 6 (high)
4
4
3
MENU
E (On)
E OFF
Selects Energy Management Recovery (EMR) 
on or off
5
4
MENU
CR Heat
(ME)
FA, SL 
Adjustable Anticipation (Heat) (only when 
SS/HP switch is at the SS position)
6
5
MENU
CR Cool
(FA)
SL
Adjustable Anticipation (Cool) (only when 
SS/HP switch is at the SS position)
7
5
MENU
CR Heat Pump
(FA)
SL
Adjustable Anticipation (Heat Pump) 
(only when SS/HP switch is at the HP position)
8
6
6
MENU
CL (OFF)
CL On
Compressor Lockout Time
9
7
7
MENU
Auto Heat
Cool Off
Heat Cool Off,
Heat Off with Fan icon,
Heat Off without Fan
icon, Cool Off,
Auto Off
System Mode Confi guration 
with Automatic Changeover
10
8
8
MENU
L (On)
L OFF
Selects Display Light on or off
11
9
9
MENU
0 HI
1 HI, 2 HI, 3HI, 4 HI,
1 LO, 2 LO, 3 LO, 4 LO
Adjustable Ambient Temperature Display
12
10
10
MENU
F
C
Selects Fahrenheit/Celsius Temperature Display
13
11
11
MENU
Change Filter (OFF)
Change Filter On
Selects Filter Change-out Indicator
MENU Change Filter 200 h
25 h to 1975 h in
25-hour increment
When on, selects time in 25 hour increments 
 
 
 
 25-hour increment
14
12
12
RUN
Returns to Normal Operation