Chapter 12 Sensor Installation
Installation Manual
308014EN, Edition 4
May 2013
For Custody Transfer applications, API chapter 7 recommends a 
minimum of one temperature sensor per 3 meters (10 feet) as shown in 
Figure 12-4. Emerson Process Management/Rosemount Tank Gauging 
may in some cases recommend a higher number of temperature sensors 
for tanks used for Custody Transfer, depending on how the tanks are 
operated.
Figure 12-4. Recommended temperature sensor positions for 
Custody Transfer Applications according to API.
Example
5 spot sensors and H=12 m.
A=12/(5-1)=3 m.
For configuration of temperature sensors see the TankMaster WinSetup 
Reference Manual
.
The temperature sensor positions to be configured in TankMaster 
WinSetup
 are measured from the tank Zero Level as illustrated in Figure 