Rosemount Tank Radar REX
Chapter 7 Bus Modems
7-12
Installation Manual
308014EN, Edition 4
May 2013
Below follows a short configuration description. Details are described in 
the Enraf Emulation Guideline (reference number 308013EN) and in 
TankMaster WinSetup Reference Manual (reference number 
303027EN).
Step 1
Connect the EBM.
Step 2
Configure the gauge in WinSetup.
Step 3
Install a tank in Winsetup: Required only for Hybrid / LPG systems 
for which the analog inputs are used. However it is a good idea to 
install a tank and associate a gauge to it, because then it is possi-
ble to benefit from the Open Tank View function.
Step 4
Configure the gauge by using the Hybrid Calculation window 
(Hybrid 
system) or LPG Setup window (LPG system) in Winsetup. 
Step 5
Set holding registers for free water level measurements.
Step 6
Enter information into the Enraf Emulation window in WinSetup. 
Set Enraf mode and move EBM switch from Modbus to Normal 
(Enraf).
Step 7
Close Enraf Emulation window. The gauge now acts like an Enraf 
instrument and the EBM can be disconnected. Connect the field-
bus to the CIU.