Emerson 308014EN Manuel D’Utilisation

Page de 166
8-5
Rosemount Tank Radar REX
Chapter 8 Junction Boxes
Installation Manual
308014EN, Edition 4
May 2013
8.3
Connection of Temperature Sensors
8.3.1
Junction Box JBT
The JBT has two openings for M25 glands suitable for 9-16 mm cables. 
Temperature sensors are attached directly to the JBT as illustrated in 
Fig. 8-5 and Fig. 8-6. Up to six temperature sensors can be connected 
via the JBT to the REX gauge or to a Data Acquisition Unit (DAU).
Figure 8-5.
Direct connection of temperature sensors to JBT 
and TankRadar REX with Remote Display Unit 40 
(RDU40).
Figure 8-6.
Direct connection of temperature sensors to JBT 
and TankRadar REX with DAU.
6.767
Level
m
JBT_RDU_REX.eps
Temperature Sensor Pt 100
(up to 6 sensors to a 
TankRadar REX gauge)
Up to 6 sensors to a 
TankRadar REX gauge
JBT_DAU_REX.eps
DAU
Temperature Sensor Pt 100 
(up to 14 sensors)
Connection to a DAU for up 
to 14 temperature sensors