GE C11 Manuel D’Utilisation

Page de 98
-22- 
 
Classifi- 
cation 
Termi-
nal 
symbol
 
Terminal name 
Detailed specifications 
Remarks 
Analog 
output 
FM, 11  Analog monitor 
Data selected between the following items is 
output with DC voltage: 
Output frequency 
PID feedback value 
Output current 
DC link circuit voltage 
* Up to two analog voltmeters (input imped-
ance : 10 k
Ω
 can be connected. 
Note: Output waveform:  An AC pulse is out-
put with consistent frequency and variable 
duty.  The average DC voltage is proportional 
to output frequency and output current (fre-
quency : 121.6 Hz). 
 
Contact 
output 
30A 
30B 
30C 
Alarm output for any 
fault 
If the drive is stopped with an alarm, the 
non-voltage contact signal (SPDT) is output 
(Contact rating: 250V ac, 0.3 A, Power factor 
= 0.3)  
(48V dc, 0.5A for Low-voltage Directive or 
42V dc, 0.5A for UL/cUL) 
Whether an alarm is generated with an excit-
ing operation or non-exciting operation can 
be switched. 
 
 
 
Optional 
DX
+
 
DX
 
RS485 RTU commu-
nication input/output 
Terminal for RS485 communication (when 
option board is installed) 
DX
+
 : Non-inverted signal,  
DX
 : Inverted signal 
Installed on op-