6    Protective Function 
6-1 
 List of protective functions  
When the protective function is activated, drive output is instantly cut off (while the motor coasts until it is 
stopped), and an alarm is issued, and the details of the alarm are displayed on the keypad panel.
 
Table 6-1-1  List of Protective Functions  
Alarm Name 
Keypad 
panel dis-
play 
Contents of operation 
OC1 
During acceleration 
OC2 
During deceleration 
Overcurrent 
OC3 
While running at 
constant speed 
If the drive output current momentarily exceeds the over-
current detection level because of an overcurrent in the 
motor or the short-circuit in the output circuit, the output is 
shut down, an alarm is issued, and the drive is tripped. 
OU1 
During acceleration 
OU2 
During deceleration 
Overvoltage 
OU3 
While running at 
constant speed 
If the DC voltage of the main circuit exceeds the overvolt-
age detection level because of an increase in the regenerat-
ing current from the motor, etc., output is shut down, an 
alarm is issued, and the drive is tripped.  However, protec-
tion against inadvertent overvoltage loading (e.g., high-
voltage line) might not be provided. 
Undervoltage 
LU 
If the DC voltage of the main circuit falls below the undervoltage detection level 
because of a lowered power supply, output is shut down to protect the drive. If the 
restart function after momentary power failure is not activated, an alarm is issued 
and the drive is tripped. 
If the restart function is activated, the drive restarts automatically with no alarm. 
For further details of the protective function, refer to the descriptions of Function 
F14. 
Overheating of 
heat sink 
OH1 
If the temperature of the heat sink used for cooling the rectifier diodes and IGBTs 
rises because of cooling fan failure, etc., protective function is activated to stop 
operation, an alarm is issued, and the drive is tripped. 
External Alarm 
OH2 
If the control circuit terminal THR (functional change of X1 to X3 terminals) is 
set to OFF, an alarm is issued and the drive is tripped. 
Motor overload 
OL 
If the motor current exceeds the operating level set by the electronic thermal O/L 
relay, output is shut down to protect the motor, an alarm is issued, and the drive is 
tripped. 
Drive overload 
OLU 
If the output current exceeds the drive rated overload current, output is shut down, 
an alarm is issued, and the drive is tripped.