  Electrical measurements in the Main Circuit 
 
The indicated values depend on the meter types because of harmonic components included in the voltage and 
current of the main power supply (input) and the output (motor) side of the drive.  Therefore, when measuring 
with a meter for the commercial power frequency, use the meters shown in Table 8-3-1. 
  The power-factor cannot be measured using the power-factor meter available on the market which measures the 
phase difference between voltage and current.  When the power-factor must be measured, measure the power, 
voltage, and current on the input side and output side. Then, calc ulate the power-factor using the following formu-
las: 
Three-phase 
 
 
 
Single -phase 
 
 
 
 
 
Table 8-3-1  Meter for measuring the main circuit 
 
 
 
(*1) When measuring the output voltage by rectifier type meter, an error may occur. Use a digital AC power meter 
for good accuracy.  
 
 
Power factor = 
Electric power [W] 
 
3
 x Voltage [V] x Current [A] 
x 100 [%] 
Electric power [W] 
 Voltage [V] x Current [A] 
x 100 [%] 
Power factor = 