Argosy Research H-125 Series Manuel D’Utilisation
21
relaY TrOubleshOOTinG
PROBLEM
CAUSE
CORRECTION
20. Relay does not energize
A. Relay driver programmed on "Time"
A. Programmed incorrectly
A. Reprogram, see page 11
B. Faulty wire connections between
B. Check and repair wire connections
PC board and relay
C. Defective PC Board
C. Replace PC Board
D. Defective relay, See figure below
D. Replace Relay
B. Relay driver programmed on "Gallons" A. Programmed incorrectly
A. Reprogram, see page 11
B. Defective PC Board
B. Replace PC Board
C. Defective relay, See figure below
C. Replace Relay
D. Faulty meter connection
D. Repair or replace meter assembly
E. Faulty wire connections between
E. Check and repair wire connections
PC board and relay