Network variables
Table 4 shows the network variables for use with the system variable, SVx command.
The system type, fan type, and changeover type variables are determined by the controller DIP switch SW1 
setting. They can be viewed by the system variable command, but cannot be changed from the network.
Table 4.
Network variables
Variable 
number
Name
Variable data
Default value
Notes
1
System type
0, 1
0
0 = gas/electric, 1 = heat pump
2
Fan type
0, 1
0
0 = gas (no fan w/heat), 1 = electric
3
Changeover type
0, 1
0
0 = c/o w/cool, 1 = c/o w/heat
4
C/F type
0, 1
0
0 = Centigrade, 1 = Fahrenheit
5
Network address
1 to 254
1
Reserved: 0 = host, 255 = global
9
Display lock
0, 1
0
0 = unlocked, 1 = locked
10
MOT
5 to 9 minutes
6 minutes
0 = 20-second test time
11
MRT
0 to 9 minutes
6 minutes
0 = 20-second test time
12
H delta stage 1 on
0 to 8 degrees
1 degree
14
H delta stage 2 on
0 to 8 degrees
3 degrees
16
H delta stage 3 on
0 to 8 degrees
5 degrees
18
C delta stage 1 on
0 to 8 degrees
1 degree
20
C delta stage 2 on
0 to 8 degrees
3 degrees
24
Setpoint h/c delta
3 to 15 degrees
4 degrees
Minimum delta T between h/c setpoints
69
Service (test) mode
0, 1
0
1 = test mode, sets MRT/MOT = 20 seconds
74
Autosend mode
0, 1
0
0 = off, 1 = on, send temp/mode on change