DEFINITY Enterprise Communications Server Release 6
Installation and Test for Multi-Carrier Cabinets  
555-230-112  
Issue 5
May 1998
Install Telecommunications Cabling 
Page 2-29
Station Wiring Design 
2
Single modular plug-ended 4-pair station cable
 
— 
Use this cable between 
adapters and information outlets that require push-on connections. It can also be 
used when 4-pair station cables are field- terminated on the 110-type terminal 
blocks in the equipment room or satellite closet and modularly connected to 
information outlets. The station cables are available in the following lengths:
—  10 feet (3.05 m)
—  25 feet (7.62 m)
—  50 feet (15.24 m)
—  75 feet (22.86 m)
— 100 feet (30.5 m)
— 150 feet (45.72 m)
— 200 feet (61 m)
NOTE:
If more than 200 feet (61 m) of 4-pair station cable is required, a 
451A in-line adapter (double-ended modular female connector) is 
attached to the cable and a second 4-pair cable of the required 
length is plugged into the adapter. See 
Double modular plug-ended 4-pair station cable
 
— 
Use this cable to provide 
nonstandard length runs between adapters and information outlets with push-on 
connections. It can also be used between adapters and modularly connected 
information outlets. It is available in the same lengths as the single modular 
plug-ended cable.
Bulk Cable
 
— 
Same as the 25-pair cable or multiple 25-pair cable; however, the 
bulk cable is not equipped with connectors. Use this cable between the 
equipment room and satellite closets when both are equipped with punch-down 
type terminal/connecting blocks.
4-pair station cable
 
— 
Use this cable when 4-pair station cables are to be 
field-terminated on the 110-type terminal blocks in the equipment room or 
satellite closet and the information outlets require push-on connections.
451A Adapter Ordering Information
Color
Comcode
Gray
103942272
Ivory
103786240