Energy Wheel 
Does NOT Turn
Blower fan motor overloads are 
tripping and auto-resetting .
Decrease fan speed .
Possible Cause
Symptom
Corrective Action
Exhaust Only frost control 
sensors are tripping .
Adjust frost temperature sensor set point as needed .
Air seals are too tight .
See Energy Recovery Wheel under Unit Start-Up section .
‘Economizer’ sensors are 
operating .
Adjust temperature or enthalpy set points as needed .
No power to wheel motor.
Make sure wheel drive is plugged in . Verify power is 
available .
Wheel drive belt
Check for loose or broken belts . Replace belts (consult 
factory) .
One or Both 
Blowers Turn Off 
Intermittently and 
Back on After 
About 2 Minutes
Wheel motor overloads are 
tripping, due to rubbing 
between wheel and air seals .
Recheck air seals, make sure they are not too tight . See 
Energy Recovery Wheel under Unit Start-Up Section .
Fan wheel rubbing on inlet
Adjust wheel and/or inlet cone . Tighten wheel hub or bearing 
collars on shaft .
Bearings .
Replace defective bearings (s) . Lubricate bearings . Tighten 
collars and fasteners .
Wheel out of balance .
Replace or rebalance .
Loose wheel on shaft .
Tighten wheel setscrew .
Energy Wheel 
Runs Intermittently
Loose motor or blower sheave .
Tighten sheave setscrew .
Belts too loose .
Adjust belt tension after 24 hours of operation .
Belts too tight .
Loosen to maintain a 3/8 inch deflection per foot of span 
between sheaves .
Worn belt .
Replace .
Motor base or blower loose .
Tighten mounting bolts .
Build-up of material on wheel .
Clean wheel and housing .
Bearing and drive misaligned .
Realign .
Noise being transmitted by
duct .
Make sure duct work is supported properly . Make sure duct 
work metal thickness is sized for proper stiffness . Check duct 
size at discharge to ensure that air velocities are not too high .
Excessive Noise or
Vibration
Troubleshooting
#461248 IOM HRE FS
Rev . 4, April 2012
Copyright © 2012 Greenheck Fan Corp .
Warranty
Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one year from 
the purchase date . The energy recovery wheel is warranted to be free from defects in material and workmanship for a 
period of five years from the purchase date . Any units or parts which prove defective during the warranty period will be 
replaced at our option when returned to our factory, transportation prepaid .
Motors are warranted by the motor manufacturer for a period of one year . Should motors furnished by Greenheck prove 
defective during this period, they should be returned to the nearest authorized motor service station . Greenheck will not 
be responsible for any removal or installation costs .
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice .