SWITCH-POINT ADJUSTMENT 
The flow switch is factory-set to the min. flow rate. To adjust 
the device to other levels, turn the adjustment screw 
clockwise. Table 1 lists the reset points and switch points for 
water. Data for other media must be determined empirically. 
Table 1. Reset and switch points for water 
reset / switch point 
paddles (L)  pipe Ø 
rec. Q
max
 
(m
3
/h) 
min. flow 
(m
3
/h) 
max. flow
(m
3
/h) 
1" 
1" 
3.6 
0.6 / 1.0 
2.0 / 2.1 
1" 
1-1/4" 
6.0 
0.8 / 1.3 
2.8 / 3.0 
1" 
1-1/2" 
9.0 
1.1 / 1.7 
3.7 / 4.0 
1"+2" 
2" 
15.0 
2.2 / 3.1 
5.7 / 6.1 
1"+2" 
2-1/2" 
24.0 
2.7 / 4.0 
6.5 / 7.0 
1"+2"+3" 
3" 
36.0 
4.3 / 6.2 
10.7 / 11.4 
1"+2"+3" 
4" 
60.0 
11.4 / 14.7 
27.7 / 29.0 
1"+2"+3"+Z* 
4" Z 
60.0 
6.1 / 8.0 
17.3 / 18.4 
1"+2"+3" 
5" 
94.0 
22.9 / 28.4 
53.3 / 55.6 
1"+2"+3"+Z* 
5" Z 
94.0 
9.3 / 12.9 
25.2 / 26.8 
1"+2"+3" 
6" 
120.0 
35.9 / 43.1 
81.7 / 85.1 
1"+2"+3"+Z* 
6" Z 
120.0 
12.3 / 16.8 
30.6 / 32.7 
1"+2"+3 
8" 
240.0 
72.6 / 85.1 
165.7 / 172.5 
1"+2"+3"+Z* 
8" Z 
240.0 
38.6 / 46.5 
90.8 / 94.2 
*For models with the suffix “Z,” the longest paddle must be used to 
obtain the values indicated in this table. The Z = 8” paddle must be 
cut to the proper length to fit into the pipe without touching the 
inside. 
 
FIELD WIRING 
ADJUSTMENT SCREW
FOR FLOW RATE
COMMON
NORMALLY OPEN
NORMALLY CLOSED
RED
BLUE
WHITE
 
Fig. 1. Field wiring 
Connect the red and the white contacts. The contact red-
white opens when the flow drops below the switch point. 
When the flow is absent, the contact red-blue closes and can 
be used as a signal or alarm contact. 
NOTE:  If the flow switch is used as a min. flow controller, 
another device must be installed downstream for 
alarm condition activation. 
 
DIMENSIONS 
70 mm
1
26 m
m
L
3”
2”
1”
29 mm
113 mm
135 mm
65
 mm
PG11
54
 m
m
R1”
 
Fig. 2. S6065A1003 dimensions 
113 mm
135 mm
72 m
m
PG11
diameter
4.5 mm
54 m
m
90 mm
70 mm
132
 mm
52 mm
L
3”
2”
1”
29 mm
R1”
 
Fig. 3. S6065A2001 dimensions