PAGE 24 — DCA45SSIU3 50 HZ GENERATOR • OPERATION AND PARTS MANUAL — REV. #2 (12/19/08) 
OUTPUT TERMINAL PANEL FAMILIARIZATION
Connecting Loads
Loads can be connected to the generator by the Output 
Terminal Lugs
 or the convenience receptacles (Figure 10). 
Make sure to read the operation manual before attempting 
to connect a load to the generator.
To protect the output terminals from overload, a 3-pole, 
110A main circuit breaker is provided. Make sure to switch 
ALL circuit breakers to the OFF position prior to starting 
the engine.
Connecting Loads
Figure 10. 
Over Current Relay
An over current relay (Figure 11) is connected to the main 
circuit breaker. In the event of an overload, both the circuit 
breaker and the over current relay may trip. If the circuit 
breaker can not be reset, the reset button on the over 
current relay must be pressed. The over current relay is 
located in the control box.
Over Current Relay
Figure 11.