DIAGNOSTIC TESTS
TEST 27 – CHECk WIRE 18
DISCUSSION:
Wire  18  controls  sending  the  STOP  signal  to  the 
Printed  Circuit  Board.  Coach  manufacturers  some-
times  install  a  15  to  30  foot  remote  harness.  If  unit 
shuts down or will not start, a possible ground exists 
on Wire 18.
PROCEDURE:
1.  Disconnect the customer installed remote harness 
connector from the generator. Then press the gen-
erator  Start-Stop  switch  to  the  “START”  position. 
If  generator  starts  and  continues  to  run,  a  short 
is present in the coach remote harness. Repair or 
replace the remote harness.
2.  Remove  the  j1  connector  from  the  Printed 
Circuit  Board.  Set  the  VOM  to  measure  resis-
tance. Connect one test lead to Pin Location j1-
2.  Connect  the  other  test  lead  to  a  clean  frame 
ground. “Infinity” should be measured.
WIRE 18
AT PIN LOCATION B
E
G
F
H
A
B
C
D
Figure 7-31. – Remote Harness Connector
3.  Connect  one  test  lead  to  Pin  Location  B  on  the 
Remote  Harness  connector  (see  Figure  7-31). 
Connect  the  other  test  lead  to  a  clean  frame 
ground. “Infinity” should be measured.
RESULTS:
1.  If  “Continuity”  is  measured  in  Step  2,  repair  or 
replace  shorted Wire  18  between  j1  Connector 
and Start-Stop Switch.
2.  If  “Continuity”  was  measured  in  Step  3,  repair  or 
replace  shorted Wire  18  between  j1  Connector 
and remote panel connector.
3.  If Wire  18  checks  GOOD,  proceed  to  Problem  8 
(Section 6).
TEST 28 – CHECk FUEL SOLENOId 
(gASOLINE MOdELS)
DISCUSSION:
If the Fuel Solenoid fails to open, the engine will not 
start.
PROCEDURE:
1.  Remove  Control  Panel  cover.  Remove  Wire  56 
from the Starter Contactor Relay. This will prevent 
the  unit  from  cranking  during  test  (see  Figure  7-
19, Page 47).
2.  Remove  air  filter  cover.  Disconnect  Connector  2 
which connects to the fuel pump.
3.  Activate  the  Start-Stop  Switch  (SW1)  to  the 
“START”  position  and  hold. This  will  activate  the 
fuel  solenoid. The  fuel  solenoid  should  energize 
and produce an audible click. If the fuel solenoid 
does  not  operate,  proceed  to  Step  4.  Reconnect 
Connector 2 back to the fuel pump.
4.  Set the VOM to measure DC voltage. Disconnect 
Wire 14 from the Fuel Solenoid. Connect the posi-
tive (+) meter test lead to Wire 14 that goes to the 
control  panel.  Connect  the  negative  (-)  test  lead 
to  a  clean  frame  ground.  Activate  the  Start-Stop 
Switch  (SW1)  to  the “START”  position  and  hold. 
Battery voltage should be measured.
5.  Set  the VOM  to  measure  resistance.  Disconnect 
Wire  0  from  the  Carburetor  at  the  bullet  connec-
tor. Connect one test lead to Wire 0 that goes to 
the control panel. Connect the other test lead to a 
clean  frame  ground.  “Continuity”  should  be  mea-
sured.
6.  Connect one test lead to the Green Wire going to 
the carburetor. Connect the other test lead to the 
carburetor body. “Continuity” should be measured.
Short to Ground:
7.  Set  the VOM  to  measure  resistance.  Disconnect 
the  bullet  connector  going  to  the  Fuel  Solenoid. 
Connect  one  meter  test  lead  to  the  Red  Wire 
going  to  the  Fuel  Solenoid.  Connect  the  other 
meter  test  lead  to  the  Fuel  Solenoid  housing. 
A  reading  of  38.0  ohms  should  be  measured. 
If  very  low  resistance  is  measured,  a  short  to 
ground  exists.  (Fuel  Solenoid  coil  resistance  is 
approximately  38.0  ohms.  Current  draw  of  the 
Fuel Solenoid at nominal voltage is approximately 
331 milliamps or 0.331 amps).
RESULTS:
1.  If the Fuel Solenoid passes Steps 4 & 5 but does 
NOT  operate  in  Step  3,  replace  or  repair  Fuel 
Solenoid.
2.  If battery voltage is not measured in Step 4, repair 
or  replace Wire  14  between  the  4-tab  Connector 
and the Fuel Solenoid.