GENERAL INFORMATION
sEctioN 1.8
automatic oPEratiNG ParamEtErs
Part 1
Page 29
introduction
When  the  generator  is  installed  in  conjunction  with 
a transfer switch, either manual or automatic opera-
tion is possible. Manual transfer and engine startup, 
as  well  as  manual  shutdown  and  re-transfer  are 
covered  in  Section  1.7.  Selection  of  fully  automatic 
operation  is  also  discussed  in  that  section.  This 
section will provide a step-by-step description of the 
sequence of events that will occur during automatic 
operation of the system.
utility Failure
Initial  Conditions:  Generator  in  Auto,  ready  to  run, 
load  being  supplied  by  utility  source.  When  utility 
fails (below 65% of nominal), a 10 second (optionally 
programmable on the 17 and 20 kW only) line inter-
rupt  delay  time  is  started.  If  the  utility  is  still  gone 
when  the  timer  expires,  the  engine  will  crank  and 
start. Once started, a five (5) second engine warmup 
timer will be initiated.
When  the  warm-up  timer  expires,  the  control  will 
transfer  the  load  to  the  generator.  If  the  utility  power 
is  restored  (above  75%  of  nominal)  at  any  time  from 
the  initiation  of  the  engine  start  until  the  generator 
is  ready  to  accept  load  (5  second  warm-up  time  has 
not  elapsed),  the  controller  will  complete  the  start 
cycle  and  run  the  generator  through  its  normal  cool 
down cycle; however, the load will remain on the utility 
source.
crankinG
The system will control the cyclic cranking as follows:
16  second  crank,  seven  (7)  second  rest,  16  second 
crank,  seven  (7)  second  rest  followed  by  three  (3) 
additional cycles of seven (7) second cranks followed 
by seven (7) second rests.
CHOkE OPERATION:
1.  The  990/999cc  engines  have  an  electric  choke  in  the 
air box that is automatically controlled by the electronic 
control board.
2.  The 530cc engines have an electric choke on the divider 
panel  air  inlet  hose  that  is  automatically  controlled  by 
the electronic control board.
3.  The  410cc  engines  have  a  choke  behind  the  air  box 
that is automatically controlled by the electronic control 
board.
FAILURE TO START:
This  is  defined  as  any  of  the  following  occurrences 
during cranking.
1.  Not  reaching  starter  dropout  within  the  specified  crank 
cycle.  Starter  dropout  is  defined  as  four  (4)  cycles  at 
1,000 RPM.
2.  Reaching  starter  dropout,  but  then  not  reaching  2200 
RPM within 15 seconds. In this case the control board 
will  go  into  a  rest  cycle  for  seven  (7)  seconds,  then 
continue the rest of the crank cycle.
During  a  rest  cycle  the  start  and  fuel  outputs  are 
de-energized  and  the  magneto  output  is  shorted  to 
ground.
CRANkING CONDITIONS:
The following notes apply during cranking cycle.
1.  Starter motor will not engage within five (5) seconds of 
the engine shutting down.
2.  The fuel output will not be energized with the starter.
3.  The  starter  and  magneto  outputs  will  be  energized 
together.
4.  Once the starter is energized the control board will begin 
looking  for  engine  rotation.  If  it  does  not  see  an  RPM 
signal  within  three  (3)  seconds  it  will  shut  down  and 
latch out on RPM sensor loss.
5.  Once  the  control  board  sees  an  RPM  signal  it  will 
energize  the  fuel  solenoid,  drive  the  throttle  open  and 
continue the crank sequence.
6.  Starter motor will disengage when speed reaches starter 
dropout.
7.  If  the  generator  does  not  reach  2200  RPM  within  15 
seconds, re-crank cycle will occur.
8.  If  engine  stops  turning  between  starter  dropout  and 
2200 RPM, the board will go into a rest cycle for seven 
(7)  seconds  then  re-crank  (if  additional  crank  cycles 
exist).
9. Once started, the generator will wait for a holdoff period 
before starting to monitor oil pressure and oil temperature 
(refer to the Alarm Messages section for hold-off times).
10. During  Manual  start  cranking,  if  the  Mode  switch  is 
moved  from  the  Manual  position,  the  cranking  stops 
immediately.
11. During  Auto  mode  cranking,  if  the  Utility  returns,  the 
cranking  cycle  does  NOT  abort  but  continues  until 
complete. Once the engine starts, it will run for one (1) 
minute, then shut down.