GENERAL INFORMATION
sEctioN 1.7
oPEratiNG iNstructioNs
Part 1
Page 27
control panel
SET
EXERCISE
SYSTEM READY
LOW BATTERY
LOW OIL PRESSURE
HIGH OIL TEMPERATURE
OVERSPEED
RPM SENSOR LOSS
OVERCRANK
ENTER
ECS
8 kW UNITS
10-20 kW UNITS
Figure 1. Generator Control Panel
AUTO-OFF-MANUAL SWITCH:
Use this switch to (a) select fully automatic operation, 
(b) to crank and start the engine manually, and (c) to 
shut the unit down or to prevent automatic startup.
1.  AUTO position:
a.  Select AUTO for fully automatic operation.
b.  When AUTO is selected, circuit board will moni-
tor utility power source voltage.
c.  Should  utility  voltage  drop  below  a  preset  level 
and remain at such a low level for a preset time, 
circuit  board  action  will  initiate  engine  cranking 
and startup.
d.  Following  engine  startup,  circuit  board  action 
will  initiate  transfer  of  electrical  loads  to  the 
“Standby” source side.
e.  On  restoration  of  utility  source  voltage  above 
a  preset  level,  circuit  board  action  will  initiate 
retransfer back to the “Utility Source” side.
f.  Following  retransfer,  circuit  board  will  shut  the 
engine  down  and  will  then  continue  to  monitor 
utility source voltage.
2.  OFF Position:
a.  Set the switch to OFF to stop an operating engine.
b.  To prevent an automatic startup from occurring, 
set the switch to OFF.
3.  MANUAL Position:
a.  Set  switch  to  MANUAL  to  crank  and  start  unit 
manually.
b.  Engine  will  crank  cyclically  and  start  (same  as 
automatic startup, but without transfer). The unit 
will transfer if utility voltage is not available.
*
   DaNGEr: WHEN tHE GENErator is 
iNstallED iN coNJuNctioN WitH aN 
automatic traNsfEr sWitcH, ENGiNE 
craNKiNG aND startuP caN occur at 
aNY timE WitHout WarNiNG (ProViDiNG 
tHE auto-off-maNual sWitcH is sEt to 
auto). to PrEVENt automatic startuP 
aND PossiBlE iNJurY tHat miGHt BE 
causED BY sucH startuP, alWaYs sEt 
tHE auto-off-maNual sWitcH to its 
off PositioN BEforE WorKiNG oN or 
arouND tHis EQuiPmENt.
7.5 AMP FUSE:
This fuse protects the DC control circuit (including the 
circuit  board)  against  overload.  If  the  fuse  element 
has melted open due to an overload, engine cranking 
or  running  will  not  be  possible.  Should  fuse  replace-
ment  become  necessary,  use  only  an  identical  7.5 
amp replacement fuse.
SETTING THE EXERCISE TIMER:
This  generator  is  equipped  with  an  exercise  timer. 
Once  it  is  set,  the  generator  will  start  and  exercise 
every seven days, on the day of the week and at the 
time  of  day  specified.  During  this  exercise  period, 
the  unit  runs  for  approximately  12  minutes  and  then 
shuts down. Transfer of loads to the generator output 
does not occur during the exercise cycle unless utility 
power is lost.
8kW:
A  switch  on  the  control  panel  (see  Figure1)  permits 
selection of the day and time for the system to exercise. 
At the chosen time, perform the following sequence to 
select the desired day and time of day the system will 
exercise. Remember seasonal time changes affect the 
exercise settings.
1.  Verify that the AUTO-OFF-MANUAL switch is set to AUTO.
2.  Press  and  hold  the “Set  Exercise”  switch  for  several 
seconds. All the red LED’s will stop flashing immediately 
and the generator will start.
3.  The  generator  will  start  and  run  for  approximately  12 
minutes and then shut down. The exerciser is now set to 
run at this time of day each week.
Example:  If  the  “Set  Exercise”  pressed  on  Saturday 
afternoon  at  2:00  p.m.,  the  generator  will  start  and 
exercise for approximately 12 minutes every Saturday 
at 2:00 p.m.
note: the  exerciser  will  only  work  in  the  auto 
mode  and  will  not  work  unless  this  procedure 
is  performed. the  exerciser  will  need  to  be  reset 
every time the 12 Volt battery is disconnected and 
then  reconnected,  and  when  the  fuse  is  removed 
and/or replaced.