3M DL Manuel D’Utilisation

Page de 168
98      Speech Intelligibility  
                 STI-PA testing
 
 
 
Models SE and DL 
Speech Intelligibility 
Another available add-on feature is 
Speech Transmission Index (STI) used to 
evaluate and classify speech intelligibility dependent of background noise level.  STI 
is the standardized measurement in the IEC 60268-16:1998 standard. 
 
STI-PA testing 
STI refers to the amount of modulation preserved in the broadcasting of an artificial 
speech signal through an alarm system.  The intelligibility measurement is a single 
value between zero and one, which factors in corruption of speech, with modulating 
speech frequencies over octave bands between 125Hz to 8kHz.  
 
STI-PA is measured using seven octave bands and 2 modulation indices per octave 
band simultaneously allowing a 15 second measurement.  In essence, any noise 
which masks (or corrupts) the talker-to-listener path is evaluated and a recommended 
measurement is computed at the end of an intelligibility test.  The following sections 
briefly address points to consider when setting up a STI-PA test. 
 
 Zones 
Where do I measure speech intelligibility?” A building or stadium can be 
broken into “zones”. Each “zone” has a room with one alarm system.  In 
some situations, one room may have more than one alarm system or may 
have a change in ceiling height (such as an atrium or a balcony seating 
versus lower level seating).   In those instances, each section would be 
considered a zone and each zone would be tested.   
After determining the “zones” in your building, it is recommended to design a 
map of the key zones/rooms.  Generally, a zone is a 20X20 area.  If the room 
is larger than 20X20, it is recommended to take another measurement in this 
section.  
 
Selecting STI scale or CIS scale 
 
With the SoundPro, you have two measurement options which will determine the 
intelligibility of your building which are the STI scale and the CIS scale (explained 
below.)