Siemens 9350 Manuel D’Utilisation

Page de 176
9300 Series User’s Guide
Data Logging Setup
Chapter 3 - Default Meter Functionality 
Page 47
Sag/Swell Logging (9350 only)
The meter logs the following output register values:
Changing the Frequency of Logging
The two Periodic Timer modules that control the frequency of different data 
recording are as follows:
“EgyDmd Log” Trg controls the frequency of logging for the Energy and 
Demand Log (this log is used for generating reports using Reporter).
“Hist Log Trg” controls the frequency of Historic Data logging.
Change the value in the Period setup register to change the frequency of data 
logging (Period values are specified in seconds). Do not change the Sync Mode 
setup register.
Changing the Log Depths
Change the value in the Depth setup register to increase the number of records 
stored in the recorder. The RecordMode setup register controls how the Data 
Recorder will overwrite old records; refer to the Data Recorder module description 
in the online ION Programmer’s Reference before changing this setup register.
Changing Waveform Recording
The Waveform Recorder modules do not require changes to their default settings. 
If you want to change the format of the recorded waveforms, refer to the 
Waveform Recorder module description in the online ION Programmer’s Reference.
Changing the Parameters that are Logged
The meter’s factory configuration logs a comprehensive set of energy, power and 
harmonics parameters. You cannot change which parameters are logged by 
configuring a setup register. Adding or deleting a log’s parameters is an advanced 
procedure, as it requires changes to the links between modules.
The software “Using Designer software” section of Using WinPM.Net describes 
adding and deleting links between modules. Once you are comfortable editing 
module links, change logged parameters by linking the output registers you want 
logged to the inputs of an ION Data Recorder module.
Sag/Swell Log
SS1 DistDur
SS1 DistV1Min
SS1 DistV1Max
SS1 DistV2Min
SS1 DistV2Max
SS1 DistV3Min
SS1 DistV3Max
SS1 DistNominal