Omega CNI8 Manuel D’Utilisation

Page de 72
30
ANALOG OUTPUT ENABLE/DISABLE SUBMENU:
Press 
b
5) Scroll though the available selection until 
ENBL displays to
use Analog Output Retransmission (output proportional to the
input signal).
Press 
d
6) Display shows 
STRD stored message momentarily and then
advances to 
CURR or VoLT Submenu only if it was changed,
otherwise press 
a to advance to CURR or VoLT
Current/Voltage Submenu.
If 
DSBL Analog Output Disabled was selected, all submenus of Analog
Output Menu will be skipped and the meter will advance to 
ALR2 Alarm 2
Menu. If 
ENBL Analog Output Enabled was selected, Output 1 would be
automatically Disabled, and reassigned as Analog Output.
CURRENT/VOLTAGE SUBMENU:
Press  
d
7) Display flashes 
CURR Current or VoLT Voltage.
Press  
b
8) Scroll through the available selection: Current or Voltage
(Example
VoLT ).
Press  
d
9) Display shows 
STRD stored message momentarily and then
advances to 
RD1 Submenu only if it was changed, otherwise
press 
a to advance to RD1 Reading 1 Submenu.
READING 1:
Press  
d
10) Display flashes 1
st
digit of previous “Reading 1” value.
Press  
b & c 11) Enter “Reading 1” value. (Example 0000)
Press  
d
12) Display advances to 
OUT.1 Out 1 Submenu.
OUT 1:
Press  
d
13) Display flashes 1
st
digit of previous “Out 1” value.
Press  
b & c 14) Enter “Out 1” value. (Example 00.00)
Press  
d
15) Display advances to 
RD!2 Reading 2 Submenu.
READING 2:
Press  
d
16) Display flashes 1
st
digit of previous “Reading 2” value.
Press  
b & c 17) Enter “Reading 2” value. (Example 9999)
Press  
d
18) Display advances to 
OUT.2 Out 2 Submenu.
OUT 2:
Press  
d
19) Display flashes 1
st
t
digit of previous “Out 2” value.
Press  
b & c 20) Enter “Out 2” value. (Example 10.00)
Press  
d
21) Display advances to the 
ALR2 Alarm 2 Menu.
The above example is for 0-10 V of the entire range of the Process Input
and Analog Output. For 0-20 mA output you need to set “Analog Type” to
Current and OUT 2 to 20.00.