Raypak  water  heaters  can  operate  lime/scale-free
using potable water with a hardness not exceeding 25
grains per gallon. Proper operation is achieved by set-
ting the temperature rise/water flow per the guidelines
in  the  installation  instructions.  If  the  hardness  of  the
water exceeds the maximum level of 25 grains per gal-
lon special measures must be taken to adjust flow and
temperature rise. Water should be softened to a hard-
ness  level  no  lower  than  5  grains  per  gallon.  Water
softened  as  low  as  0  to  1  grain  per  gallon  may  be
under-saturated  with  respect  to  calcium  carbonate
resulting in water that is aggressive and corrosive.
pH of Water
pH is a measure of relative acidity, neutrality or alka-
linity. Dissolved minerals and gases affect water’s pH.
The pH scale ranges from 0 to 14. Water with a pH of
7.0 is considered neutral. Water with a pH lower than
7 is considered acidic. Water with a pH higher than 7
is considered alkaline. A neutral pH (around 7) is desir-
able  for  most  potable  water  applications.  Corrosion
damage and water heater failures resulting from water
pH levels of lower than 6 or higher than 8 are non-war-
rantable.  The  ideal  pH  range  for  water  used  in  a
storage tank or a copper water heater system is 7.2 to
7.8.
Total Dissolved Solids
Total dissolved solids (TDS) is the measure of all min-
erals  and  solids  that  are  dissolved  in  the  water.  The
concentration  of  total  dissolved  solids  is  usually  ex-
pressed  in  parts  per  million  (ppm)  as  measured  in  a
water  sample.  Water  with  a  high  TDS  concentration
will greatly accelerate lime and scale formation in the
hot  water  system.  Most  high TDS  concentrations  will
precipitate  out  of  the  water  when  heated.  This  can
generate  a  scale  accumulation  on  the  heat  transfer
surface  that  will  greatly  reduce  the  service  life  of  a
water  heater.  This  scale  accumulation  can  also
impede adequate flow of water and may totally block
the water passages in the tubes of the heat exchang-
er. A  heat  exchanger  that  is  damaged  or  blocked  by
lime/scale accumulation must be replaced. Failure of a
water heater due to lime scale build up on the heating
surface  is  non-warrantable.  The  manufacturer  of  the
water heater has no control of the water quality, espe-
cially  the  TDS  levels  in  your  system.  Total  dissolved
solids in excess of 2,500 ppm will accelerate lime and
scale formation in the heat exchanger. Heat exchang-
er  failure  due  to  total  dissolved  solids  in  excess  of
2,500  ppm  is  a  non-warrantable  condition.  Raypak
offers basic temperature guidelines for operation of a
potable water heater on normal to moderate levels of
hardness  and  solids  but  levels  of  hardness  and  total
dissolved solids beyond normal limits for operation will
require special setup and operation.
NOTE: Failure  of  a  heat  exchanger  due  to  lime
scale  build-up  on  the  heating  surface,  low  pH  or
other chemical imbalance is non-warrantable.
Table J: Water Chemistry
Recommended Level(s)
Fiberglass Pools
Fiberglass Spas
Other Pool and Spa
Types
Water Temperature
68-88°F (20-31°C)
89-104°F (31-40°C)
68-104°F (20-40°C)
pH
7.3-7.4
7.3-7.4
7.6-7.8
Total Alkalinity (ppm)
120-150
120-150
80-120
Calcium Hardness (ppm)
200-300
150-200
200-400
Salt (ppm)
3000 Maximum
3000 Maximum
3000 Maximum
Free Chlorine (ppm)*
2-3
2-3
2-3
Total Dissolved Solids
(ppm)
1500 Maximum**
1500 Maximum**
1500 Maximum**
*Free Chlorine MUST NOT EXCEED 5 ppm!
**In salt water chlorinated pools, the total TDS can be as high as 4500ppm
NOTE: The allowable concentrations of salt and of the Total Dissolved Solids are lower for the Hi Delta than
for a typical residential pool heater, due to the higher water temperatures at which a Hi Delta operates.