Siemens SINVERT 350 Manuel D’Utilisation

Page de 42
Alarm and fault messages 
4.2 Alarm and fault messages  
33 
Table 4-9 Fault 36 
(Alarm) AC contactor defective (no checkback), or Fast Stop button pressed 
Condition 
There is no signal at input 11/12 of the CU (green 
connector); transferred via Profibus to the S7; drive has 
received an ON command. 
No power supply for Fast OFF  
o
  Fast Stop button has been pressed 
o
  Wire break in the Fast OFF circuit 
o
  Defect in power supply for Fast OFF 
o
  Fire alarm system has been activated (if 
installed) 
Causes 
No checkback signal from the AC contactor 
o
  Defect in AC contactor control circuit (power 
pack) 
o
  Defect in AC contactor coil 
o
  Defect in auxiliary contacts of AC contactor 
o
 Wire 
break 
Unlock the Fast Stop button. 
Replace the AC contactor 
Unlatch the contacts of the AC contactor 
 
Measures 
Repair the cabling 
 
Table 4-10 Fault 37
 
(Alarm) Several restart attempts in succession 
Condition 
The S7 has tried several times without success to 
restart the drive 
Fault in the drive 
Causes 
Operational fault (might be rectified automatically) 
 
Measures 
Repair the drive