Introduction
11/2
Siemens ST PCS 7 · November 2007
11
Overview
The SIMATIC PCS 7 process control system offers various pos-
sibilities for connecting I/O devices and for detecting and emit-
ting process signals through sensors and actuators: 
• Analog and digital I/O modules of the SIMATIC S7-400 oper-
ated centrally in the automation system
• ET 200M, ET 200S, ET 200iSP and ET 200pro remote I/O sta-
tions with an extensive range of cost-effective signal and func-
tion modules, connected through PROFIBUS DP to the auto-
mation system (AS)
• Direct AS connection of intelligent, distributed field/process 
devices and operator terminals through PROFIBUS DP/PA (re-
dundant or in hazardous zones 0, 1, 2 or 20, 21, 22 also pos-
sible)
Signal groups of the SIMATIC S7-400 can be operated centrally 
in the automation system and are mainly used in small applica-
tions or systems of limited distributed expansion.
Distributed process I/Os are mainly used nowadays: ET 200 
remote I/Os in conjunction with classical field/process devices 
and HART field devices or intelligent field/process devices di-
rectly on PROFIBUS. Decisive for this are properties such as:
• Modularity and consistency
• Flexible adaptability to the plant structure
• Minimum cabling and engineering requirements
• Low commissioning, servicing and lifecycle costs
• Wide technical bandwidth
Design
Integration of I/O modules in the hazardous area
ET 200 in explosive gas and dust atmospheres
1)
Dust atmospheres: installation of components always in an enclosure with IP6x degree of protection.
2)
With 10 A DC standard power supply
3)
Also complies with FM/UL according to Class I Division 2
The diagram shows the various interfacing possibilities for the 
distributed I/Os of SIMATIC PCS 7 with consideration of various 
ambient conditions.
0
1
2
FM/UL
ATEX
ATEX
Zone 2
Zone 1
Zone 0
Class I Zone 2
Class I Zone 1
Class I Zone 0
ET 200M
S7-400
ET 200S
ET 200iSP
SITRANS F
SITRANS P
Industrial Ethernet
PROFIBUS DP
PROFIBUS PA
Zone 22
Zone 21
Zone 20
Class II Zone 2
Class II Zone 1
Class II Zone 0
FM/UL
1)
1)
1)
1)
2)
1) 3)
Ex e, Ex d
Ex i, Ex e, Ex d
Ex i
DUST
GAS
Process control system
Fieldbus
Isolating Transformer
Hazardous area
Actuators/
sensors
Actuators/
sensors
Actuators/
sensors 
DP/PA link
Actuators/
sensors
© Siemens AG 2007