“B” Group: Fine-Tuning Functions
Configur
ing Dr
iv
P
a
ra
meters
3–44
B090: Dynamic braking usage ratio – This parameter limits the amount of time the inverter 
can use the dynamic braking accessory device without entering the Trip Mode. Please refer to 
 for more information on dynamic braking accessories.
NOTE: When cooling fan control is enabled (B092=01) the inverter always turns the fan ON 
for 5 minutes immediately after powerup. This will cool the inverter in case the inverter / motor 
is still warm from prior running before a short power outage.
B090
Dynamic braking usage 
ratio
Selects the braking duty 
cycle for the dynamic 
braking resistor (total brake 
% ON-time per 100 sec. 
interval).
Range is 0.0 to 100.0%
0%Dynamic braking 
disabled
>0% Enabled, per value
✘ ✔
00
00
00
>b090 BRD
%ED       000.0%
B091
Stop mode selection
Selects how the inverter 
stops the motor, two option 
codes:
00 DEC (decelerate and 
stop)
01 FRS (free run to stop)
✘ ✘
00
00
00
>b091 RUN
STOP         DEC
B092
Cooling fan control
(see note below)
Two option codes:
00 Fan always ON
01 Fan ON during RUN, 
OFF during STOP
✘ ✘
00
00
00
>b092 INITIAL
FAN-CTL      OFF
B095
Dynamic braking 
control
Three option codes:
00 Disable
01 Enable during RUN only
02 Enable always
✘ ✔
00
00
00
>b095 BRD
Mode   OFF
B096
Dynamic braking 
activation level
Range is:
330 to 380V (200V class),
660 to 760V (400V class)
✘ ✔ 360/
720
360/
720
360/
720
V
>b096 BRD
LEVEL     360Vdc
B098
Thermistor for thermal 
protection control
Three option codes:
00 Disable
01 Enable-PTC thermistor
02 Enable-NTC thermistor
✘ ✔
00
00
00
>b098 THERM
SELECT       OFF
B099
Thermal protection 
level setting
Thermistor resistance 
threshold at which trip 
occurs.
Range is 0.0 to 9999 Ohms
✘ ✔ 3000 3000 3000
Ohms
>b099 THERM
LEVEL    3000ohm
“B” Function
Run 
Mode
Edit
Lo Hi
Defaults
Units
SRW Display
Func.
Code
Name
Description
–FE
(CE)
–FU
(UL)
–FR
(Jpn)