Figure 1-1. Operational Flow Charts (1 of 2)
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.8.5153
Section 1 • Operational Flow Charts
Volume and 
Capacity slides are 
less than 5%
Oil Separator Temp 
>Oil Sep Start Trip 
Setpt
Filter Diff Press < 
Start Filter Diff Trip 
Setpt
Oil Pump On: Prelub Oil Press is > Prelub Oil
Press Reset Setpt for “Min Compressor Prelub Timer” 
setting (typically 5 seconds)
Start Compressor
Start 
Compressor
Is
Run Oil Press>
Prelub Oil Press
Reset setpt?
(Default 5 PSI)
Is
Run Oil Press>
Run Oil Press
Reset setpt?
(Default 40 PSI)
“Oil Press
Bypass at Comp 
Start” timer
expires (60 sec 
after start)
Run Oil Press Failure
Run Oil Press Failure
“Filter Diff Press Safety
Changeover” timer expires 
(60 sec after start)
Is Filter Diff >
Hi Filter Diff Press Run
Trip Setpt
for 5 seconds
Oil Separator Temp
Safety Changeover
Timer expires (5 min 
after start)
Is
Oil Sep Temp > Lo
Oil Sep 
Run Reset
setpt?
Run
Run Filter Diff Press Failure
Lo Run Oil Sep Temp Failure
Is
Motor Amps >
FLA (ON)
Setpt?
Is
Dsch Press >
Cutin (ON)
Setpt?
Is
Dsch Press >
Cutout (OFF)
Setpt?
Capacity Increase
Disabled
Capacity Decrease
until Amps < FLA x 
1.0625
Normal Loading and 
Unloading
Is
Motor Amps >
FLA (OFF)
Setpt?
Capacity Increase
Disabled
Capacity Decrease until 
Dsch Press < ON Setpt x 
1.0625
Normal Loading and 
Unloading
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No
No
Requirements to Start Compressor
Critical Compressor Run Logic at Compressor Start
Compressor Amperage Load Limiting
High Discharge Pressure  Load Limiting