Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.8.5153
enable Superheat Monitoring on the screen.
• As previously described, Cool Compression 
compressor does not have an oil pump. Instead 
it has a suction oil injection solenoid to pro-
vide oil and liquid ammonia for lubrication and 
cooling.
• Cool Compression liquid injection 1 and liq-
uid injection 2 outputs will operate as high / low 
pressure ratio solenoid outputs.  
Control Functions
In the Compressor Control Menu, special cool compres-
sion control functions are now available, see Figure 25-2. 
Cool Compression Control Functions Screen. These new 
functions are:
• Auto Load
•  Suction Oil Injection Settings
•  Danfoss Positioning Valve Settings
Auto Load
•  Auto load operation will force the compressor to 
load to a minimum value once the compressor has 
started. By loading the compressor to a minimum 
value, and maintaining this capacity, a pressure ratio 
is created across the compressor, to ensure adequate 
lubrication of the compressor, and also that the com-
pressor does not experience high discharge super-
heat conditions. Since compressor lubrication is of 
great importance, all load limiting is disabled when 
auto load is engaged.
•  Auto Load at Start 
• Defi nes the value at which Compressor (ca-
pacity slide) should be loaded (and maintained) 
at start if Auto Load is enabled.
Section 25 • Cool Compression Control
Figure 25-2. Cool Compression Control Functions Screen