Emerson 20/20 Manuel D’Utilisation

Page de 120
3 – 2
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.8.5153
Digital Input/Output (I/O)
Refer to Table 2-1. Digital I/O.
Compressor Start Output:
•  When the Vission 20/20 signals the compressor to 
start, this output is energized. When the Vission 
20/20 signals the compressor to stop, this output is 
de-energized.
Oil Pump Start Output:
•  When the Vission 20/20 signals the oil pump to start, 
this output is energized. When the Vission 20/20 sig-
nals the oil pump to stop, this output is de-energized.
Capacity Increase Output:
•  This output is only active when the compressor is 
running. When the Vission 20/20 determines that 
the compressor should increase capacity by moving 
the slide valve to a higher percentage, this output is 
energized. Once the slide valve reaches 100%, this 
output will not energize.
Capacity Decrease Output:
•  This output is only active when the compressor is 
running. When the Vission 20/20 determines that 
the compressor should decrease capacity by moving 
the slide valve to a lower percentage, this output is 
energized. Once the slide valve reaches 0%, this out-
put will not energize.
Volume Increase Output:
•  This output is only active when the compressor is 
running. When the Vission 20/20 determines that 
the compressor should increase Volume Index (VI) by 
moving the volume slide to a higher percentage, this 
output is energized. Once the volume slide reaches 
100%, this output will not energize.
Volume Decrease Output:
•  This output is only active when the compressor is run-
ning. When the Vission 20/20 determines that the 
compressor should decrease Volume Index (VI) by 
moving the volume slide to a lower percentage, this 
output is energized. Once the volume slide reaches 
0%, this output will not energize.
Oil Sump Heater Output:
•  This output is active and energized when the oil 
separator temperature is lower than the oil separator 
temperature setpoint. It is de-energized when the oil 
separator temperature is higher than the oil separa-
tor temperature setpoint.
Trip Output:
•  This output is energized when the system has no 
Trips. If a trip is issued, the output de-energizes and 
stays de-energized until the trip condition is cleared.
Slide Valve Setpoint #1 Output (Economizer):
•  Normally used for an economizer solenoid, but could 
be used for other devices. When the compressor slide 
valve percentage is equal to or greater than “slide 
valve set-point #1”, the output is energized. When 
the compressor slide valve percentage is less than 
“slide valve set-point #1”, the output is de-energized.
Slide Valve Setpoint #2 Output (Hot Gas):
•  Normally used for a hot gas solenoid, but could be 
used for other devices. When the compressor slide 
valve percentage is equal to or greater than “slide 
valve set-point #2”, the output is energized. When 
the compressor slide valve percentage is less than 
“slide valve set-point #2”, the output is de-energized.
Alarm Output:
•  This output is energized when the system has no 
alarms. If an alarm is issued, the output de-energizes 
and stays de-energized until the alarm condition is 
cleared.
Unused:
•  This output has no current function.
Liquid Injection #1 Output:
•  If the compressor has liquid injection oil cooling, this 
output is active. When the compressor is running and 
the discharge temperature is above the oil separator 
temperature override setpoint and the oil separator 
temperature is above the override setpoint, then the 
output is energized. The output is de-energized when 
the discharge temperature falls below the “on” set-
point minus the solenoid differential.
Liquid Injection #2 Output:
• Not Defi ned
Remote Enabled Output:
•  This output is energized when the Vission 20/20 
panel is enabled for remote control. The compres-
sor can be running or stopped, but is available to the 
remote system. If the compressor has an alarm or is 
placed into the manual stop position, this output is 
de-energized.
Shunt Trip:
• Not defi ned.
Comp Motor Starter Auxiliary Contact:
•  This input looks for a feedback signal from the com-
pressor starter, confi rming that the compressor 
starter is energized.
Section 3 • Hardware Architecture