Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.8.5153
due to repeated motor starts. The operator has 3 choices 
of protection. Hot starts allows only a certain number of 
starts per hour before setting an hour to the anti-recy-
cle timer. The number of starts is set in the timer page. 
Accumulative immediately adds time to the anti-recycle 
timer once the compressor is started and the time can 
be set in the timers screen. True anti-recycle adds to the 
anti-recycle timer once the compressor is shutdown. The 
motor of the compressor can not be restarted as long as 
there is anti-recycle time left and the operator can view 
this time on the top left corner of the main screen.
Restart On Power Failure
This feature of the Vission 20/20 offers the ability to de-
fi ne how the Vission 20/20 will handle a power failure. 
This can also be useful to allow system controller to re-
gain control of the Vission panel without the need for 
operator intervention.
Always:
•  When selected, initiates a start after the panel pow-
ers back up after a power failure, but only if the com-
pressor was running before the power failure and 
starts the compressor in Auto mode.
Never:
•  When selected, prevents any automatic action once 
the panel powers back up after a power failure.
Timed:
•  When selected, initiates a start after the panel pow-
ers back up after a power failure and the operator set 
timer runs out. When there are multiple compressor 
in a larger system, it is recommended that the opera-
tor gives each compressor a different start times. A 
restart will only occur if the compressor was running 
before the power failure and starts the compressor in 
Auto mode.
Remote Lock Off:
•  When selected, turns the remote lock out off when 
the panel powers up. Select this option if the opera-
tor wishes a system controller to regain control of the 
Vission 20/20 without human interference.
Boot in Remote (Direct I/O)
•  When selected, places the panel into remote mode 
when the panel powers up. Select this option when 
under direct I/O control and the system controller is 
to gain control of the Vission 20/20 without human 
interference.
Compressor Sequencing
The compressor sequencing is a feature of the Vission 
20/20 that allows the operator to setup as many as fi ve 
compressor to automatically start, stop and maintain 
system loads. The compressor that is designated as the 
master will monitor systems parameter and make deci-
sions on how many compressor are required to meet the 
load as effi ciently as possible.
Compressor Sequencing:
•  Enables the compressor sequencing algorithms and 
allows access to the compressor sequencing screen.
Master:
• Identifi es the panel as the master while in sequencing 
control.
Slave:
• Identifi es the panel as a slave while in sequencing 
control.
Compressor Name:
• Unique identifi er that is broadcasted to all other 
Vission 20/20 units in the sequencing network.
Language
Allows the operator to select the language in which all 
screens will be displayed in.
Model & Refrigerant
The values in this section provides the Vission 20/20 
algorithm critical information on how to effi ciently 
and safely control the compressor, see Figure 19-2. 
Confi guration Screen - Page 2.
Compressor:
•  Drop-down box to select the compressor type. This 
selection is critical for proper volume slide control.
Model:
•  Drop-down box to select the compressor size. This 
selection is critical for proper volume slide control.
Refrigerant:
•  Drop-down box to select the type of refrigerant. This 
selection is critical for proper volume slide control.
Other (K-Factor):
•  Optional setting to adjust volume slide control.
Section 19 • Configuration