ICM/ICAD Motorized Valve Setup Instructions
The following items need to be setup in order for the valve to operate properly.
1.  Press the “Circle” button on the valve.  A value of “01” should be shown on the screen.
2.  Press the “Circle” button.  There should be a value of “1” shown.  If not use the up/down 
arrows to change it to the correct value.  Press the “Circle” button when done.
3.  Press the “Up” arrow button.  A value of”02” should be shown on the screen.
4.  Press the “Circle” button.  There should be a value of “1” shown.  If not use the up/down 
arrow buttons to change it to the correct value.  Press the “Circle” button when done.
5.  Press the “Up” arrow button.  A value of “03” should be shown on the screen.
6.  Press the “Circle” button.  There should be a value of “2” shown.  If not, use the up/down 
arrow buttons to change it to the correct value.  Press the “Circle” button when done.
7.  Press the “Up” arrow button until a value of “04” is shown on the screen.
8.  Press the “Circle” button.  There should be a value of “50” shown.  If not, use the up/down 
arrow buttons to change it to the correct value.  Press the “Circle” button when done.
9.  Press the “Up” arrow button until a value of “07” is shown on the screen.
10. Press the “Circle” button.  There should be a value of “1” shown.  If not, use the up/down 
arrow buttons to change it to the correct value.  Press the “Circle” button when done.
11. Press the “Up” arrow button until a value of “10” is shown on the screen.
12. Press the “Circle” button.  Press the up/down arrow button to change the value to “11”.  
Press the “Circle” button.
Danfoss Liquid Injection Valve Setup