ICM/ICAD Motorized Valve 
 
 
Installation, Programming, and Troubleshooting
¢ Danfoss (USCO / MKS), 11 - 2006
 
DKRCI.EI.HT0.A1.22 / 520H1639 
 
       11
Alarms
There are a number of alarms which are excellent indicators of improper installation or
set-up:
Description
ICM
alarm text
Comments
No valve type selected
A1
At start-up A1 and CA will be displayed
Controller fault
A2
Internal fault inside electronics
Input error
A3
Not applicable if ¡01 = 2 or ¡02 = 2
When ¡03 = 1 and AI > 22 mA
When ¡03 = 2 and AI > 22 mA or AI < 2 mA
When ¡03 = 3 and AI >12 V
When ¡03 = 4 and AI >12 V or AI < 1 V
Low voltage of fail safe supply
A4
If 5 V d.c. < Fail safe supply 
< 18 V d.c.
Check Supply to ICAD
A5
If supply voltage < 18 V d.c.
Problem
Possible cause and solution
The valve is not working and an A1 is 
flashing in the display.  
The ICM valve size was not selected in 
parameter 
¡26
.  See the programming 
section on page 9.
The valve does not appear to be opening 
or closing properly
The ICAD was not mounted properly 
on the valve stem.  Solution:  Check to 
make sure that the ICAD was mounted 
evenly on the ICM valve
The ICAD is not receiving a proper 
input signal.  Solution:  Use the service 
parameters (
¡51
 for a mA input or 
¡52
 
for a voltage input) to check the input 
signal that the ICAD is receiving.
1.
2.
The valve position feedback signal is not 
working when using customer supplied 
controller/PLC
A power supply was installed in the 
4-20mA/0-20mA feedback loop.  
The ICAD motor actuator supplies 
the power for the 4-20mA/0-20mA 
feedback loop.  Solution:  Remove any 
power source that may be supplied to 
the feedback loop.  
Wiring problem.  Solution:  Check the 
service parameter 
¡53
 to see what the 
ICAD is outputting.  If this does not 
reveal anything, check the current 
output (yellow and blue wires in ICAD 
control cable) with an ammeter. 
The feedback output signal was turned 
off in parameter 
¡06
.  Solution:  Check 
to make sure the setting in parameter 
¡06
 is correct.
1.
2.
3.
For all other problems, contact Danfoss.