Stop Check Valve Operation
AUTO
In the “Auto Position”, the stop valve is 
operating as a check valve, allowing fl ow 
in the directions of the arrows. 
To set the valve to the automatic posi-
tion, fully close the valve, and turn the 
stem out as indicated by the chart below.
CLOSED
In the manually “Closed Postion”, the 
stop check is operating as a conventional 
stop valve, not allowing fl ow in either 
direction.
OPEN
In the manually ” Open Position”, with 
the valve stem fully back seated, the 
valve disc is lifted slightly, allowing fl ow 
in either direction.
Valve 
Size      1.5” 
2” 2.5” 
3” 4” 5” 6” 8”
Number 
of 
Turns 
Open  
2.25 2.75 3.25 4.5  3.75 5.75 7.75
(from closed position)