Emerson VSR Manuel D’Utilisation

Page de 145
87
Maintenance
NOTE: See Motor Manual for proper lubrication procedures and service intervals. 
Refrigeration Maintenance and Inspection Schedule
The following service intervals are based on the usage of Vilter Manufacturing Corporation Premium Grade refrig-
eration oil in VSS, VSM and VSR Single Screw Compressor units.
 
 
SERVICE INTERVAL (HOURS)
 
OIL CIRCUIT 
 
Oil 
Change 
(1) 
 R  R  R  R  R  R  R 
 
Oil 
Analysis 
(2) 
  S S S S S S S S S S S S S 
 
Oil 
Filters 
(3) 
R R R R R R R R R R R R R R 
 
Oil 
Strainer 
I I I I I I I I I I I I I I 
PACKAGE 
 
Coalescing 
Elements     R   R   R   R 
 
Suction 
Screen 
I I I I I I I I I I I I I I 
 
Liquid 
Line 
Strainers  I I I I I I I I I I I I I I 
 Coupling 
Alignment 
 
and 
Integrity 
I I I I I I I I I I I I I I 
CONTROL  
CALIBRATION  Transducers 
I I I I I I I I I I I I I I 
 
RTD’s 
I I I I I I I I I I I I I I 
COMPRESSOR 
 
Inspect 
Compressor  I  I  I  I  I  I  I 
 
Bearings 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Key I  Inspect. 
   R  Replace. 
   S  Sample. 
Notes: 
(1)  The oil should be changed at these intervals, unless oil analysis results exceed the allowable limits.   
 
 
The frequency of changes will depend on the system cleanliness.
 
 
(2)  Oil analysis should be done at these intervals as a minimum; the frequency of analysis will depend on  
  
system 
cleanliness.
 
 
(3)  The oil filter(s) on a minimum must be changed at these intervals or annually if not run continuously.   
 
 
However, the oil filter(s) must be changed if the oil filter differential exceeds 12 psi or oil analysis    
  
requires 
it. 
200
5,000
10,000
20,000
30,000
40,000
50,000
60,000
70,000
80,000
90,000
100,000
110,000
120,000
 
 
 
Inspection
 
 
 
        Or 
Group 
  Maintenance
 
 
 
       Item