VSG/VSSG • Installation, Operation and Maintenance Manual •Vilter/Emerson • 35391SSG
Section 4 • Operation
Operation
All operation (setpoint adjustments, calibrations, 
monitoring) of the compressor unit is done through 
the Compact Logix PLC. For additional procedural 
information, refer to Compact Logix PLC Software 
Manual (35391CL).
Oil Inspection
WARNING
When working with LFG, NG or other dangerous
or  fl ammable gases, ensure there are adequate
ventilation and vapor detectors. Refer to national fi re
and building codes. Failure to comply may result in
serious injury or death.
WARNING
Avoid skin contact with any condensate or oil. Wear
rubber gloves and a face shield when working with
condensate or oil. Failure to comply may result in
serious injury or death.
Inspect oil level through sight glasses on the oil 
 Figure 4-1. Oil Operating Levels
Normal Operating Level
Maximum NON-Operating Level
Minimum Operating Level
separator, see Figure 4-1. Oil Operating Levels. Drain or 
fi ll oil as required. For oil draining and fi lling procedure, 
see Oil Charging and Oil Draining in Section 5.Oil Flow 
with Dual Oil Filters
Dual Oil Filters
On compressor units equipped with dual oil fi lters, only 
one fi lter should be in operation at a time.
NOTE
During operation, both oil fi lter outlet shut-off valves 
should be open. This will help minimize the sudden loss 
of oil pressure when switching between oil fi lters for 
servicing.
Refer to Oil Filter Replacement in Section 5 for further 